Heating Stage 3 PGM<br />

The heat 3 PGM is activated when the RTHP has a requirement for heating and the heating<br />

stage demand value has been exceeded for the third stage. The heating 3 PGM will typically<br />

be used to control the third stage of the heating system.<br />

FN001 Heat 3<br />

pgm: --000:00<br />

To modify the heat 3 PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

Heating Stage 4 PGM<br />

The heat 4 PGM is activated when the RTHP has a requirement for heating and the heating<br />

stage demand value has been exceeded for the fourth stage. The heating 4 PGM will typically<br />

be used to control the fourth stage of the heating system.<br />

FN001 Heat 4<br />

pgm: --000:00<br />

To modify the heat 4 PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

Dehumidification Stage 1 PGM<br />

The dehumidification stage 1 PGM is activated when the RTHP has a requirement for<br />

dehumidification. The dehumidification process will typically open the first stage of the hot gas<br />

reheat valves located in the RTHP unit.<br />

FN001 Dehumid 1<br />

pgm: --000:00<br />

To modify the dehumidification stage 1 PGM, use the settings as explained in section Entering<br />

PGM and PGM Groups on Page 410.<br />

Dehumidification Stage 2 PGM<br />

The dehumidification stage 2 PGM is activated when the RTHP has a requirement for<br />

dehumidification and the humidity is above the hysterisis value plus the setpoint. The<br />

dehumidification process will typically open the second stage of hot gas reheat valves located<br />

in the RTHP unit.<br />

FN001 Dehumid 2<br />

pgm: --000:00<br />

To modify the dehumidification stage 2 PGM, use the settings as explained in section Entering<br />

PGM and PGM Groups on Page 410.<br />

Base Data Register<br />

The Base data register is used as the first register in the list of registers used to configure,<br />

program and control the RTHP. The only registers that are not included in the base registers<br />

are ones that must link to an analog input or analog output for external sensors (Temp,<br />

Humidity or Dampers). A base data register setting MUST be set.<br />