The RTHP (Roof Top Heat Pump / Roof Top Heat Pack) programmable function allows the<br />

direct control of multiple stage Roof Top Heat Pumps used for large retail or commercial space<br />

temperature control. There is a substantial number of configuration screens for the RTHP unit<br />

and a working knowledge of Air Conditioning and Temperature Set Point configuration is<br />

essential in setting up the correct operation of the programmable function.<br />

FN001 Func Type<br />

RTHP Control<br />

Use the [1] and [3] keys to scroll the function types until you reach the RTHP control<br />

selection and press [ENTER] to select the function type displayed and proceed to the next<br />

programmable option for the RTHP control function. For more information about the list<br />

control data entry refer to the section List Control Data Entry on Page 406.<br />

Function Mode<br />

The function mode determines how this function operates with the system controller. By<br />

default a function is set to normal operation. Normal operation will mean the function is<br />

started if it was running when the system restarts or is completely powered down (AC Failure<br />

and Battery Failure). The Run Once mode of operation will allow the function to run once and<br />

then wait to be stopped and started by the user or operator. Setting the run once option for<br />

the RTHP will result in NO operation being performed and the function stopping a short time<br />

after it is started.<br />

FN001 Func Mode<br />

Normal<br />

Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and<br />

press [ENTER] to proceed to the next programmable option for the RTHP control function.<br />

For more information about the list control data entry refer to the section List Control Data<br />

Entry on Page 406.<br />

Enabled Control PGM<br />

Enabled Control PGM is set when the RTHP is to run and will operate only when the enabled<br />

PGM is on. If no enabled PGM is set the RTHP will run continuously. This allows the RTHP to<br />

operate only during the times that the space is occupied. The signal can also be a memory<br />

register or a Boolean (bit) value from the selected memory register.<br />

FN001 Enabled<br />

pgm: --000:00<br />

To modify the occupy PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

Fault PGM<br />

The fault control PGM is set when a fault condition has occurred and the RTHP is to shutdown.<br />

This allows the RTHP to shutdown in the shortest possible time without causing any damage<br />

to the system. In the case of a fire shutdown the system must have a fire PGM programmed.<br />

FN001 Fault<br />

pgm: --000:00<br />