Area Control<br />

RTHP Control<br />

Floor Temping<br />

Value Compare<br />

Ripple PGM<br />

Door Control<br />

of the logic function however if the output is changed from the<br />

state it will be updated 30 seconds later, this prevents endless<br />

loops from occurring while still ensuring an output will result in it<br />

being maintained.<br />

Can be used to arm or disarm an area based on the status of a<br />

PGM output. This can only check the area status in follow mode<br />

every 60 seconds.<br />

Use to manage a Roof Top Heat Pack air conditioning system and<br />

can operate up to 4 stages of heat and cool as well as two stages<br />

of dehumidification.<br />

Use to manage a floor tempering system with single stage heat<br />

and cool. Duct and floor sensors inputs as well as reverse and<br />

forward operational modes.<br />

A direct comparison between two data registers with<br />

programmable hysterisis and activate time as well has a high and<br />

low PGM output. Ideal for the control of lighting circuits based on<br />

daylight sensor inputs<br />

Ripples on and ripples off up to 8 PGM outputs from an enable<br />

PGM. Ideal for staging on large current devices and multiple<br />

lighting circuits.<br />

Can be used to lock and unlock a door or door group based on<br />

the status of a input.<br />

The functions require specific programming for the type that is selected, the following details<br />

the programming information for each function type.<br />

• Logic Control (Page 278)<br />

• Area Control (Page 282)<br />

• RTHP <strong>Controller</strong> (Page 284)<br />

• Value Compare (Page 299)<br />

• Ripple PGM Output (Page 302)<br />

• Door Control (Page 305)<br />

• Floor Temping Control (Page 294)<br />

Logic Control Function<br />

To program the logic control function ensure that the function you have selected is halted.<br />

Select the function type selection screen as shown below for logic control.<br />

FN001 Func Type<br />

Logic Control<br />

Use the [1] and [3] keys to scroll the function types until you reach the logic control selection<br />

and press [ENTER] to select the logic control function type displayed and proceed to the next<br />

programmable option for the logic control function. For more information about the list<br />

control data entry refer to the section List Control Data Entry on Page 406.<br />

Function Mode<br />

The function mode determines how this function operates with the system controller. By<br />

default a function is set to normal operation. Normal operation will mean the function is<br />

started if it was running when the system restarts or is completely powered down (AC Failure<br />

and Battery Failure). The Run Once mode of operation will mean the function will only run<br />

once and then wait to be stopped and started by the user or operator.<br />

Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong><br />

278