PN001 Secondary<br />

None<br />

Use the [1] and [3] keys to scroll the secondary telephone number selection and press<br />

[ENTER] to select the telephone number displayed. For more information about the list<br />

control data entry refer to the section List Control Data Entry on Page 406. Programming a<br />

secondary telephone number that uses the current telephone number being edited will<br />

perform no function.<br />

Telephone Number<br />

Program the telephone number that you want to assign to this telephone number entry.<br />

PN001 Number<br />

Use the numeric keys [0] to [9] to enter the telephone number. When the number has been<br />

programmed press the [ENTER] key. To clear the telephone number displayed press the<br />

[DISARM] key.<br />

When using a telephone number that requires a number to be dialled before gaining an<br />

outside line program the individual number or series of numbers in to a telephone number<br />

and call this 'PABX Access'. When programming the service or function that requires the<br />

telephone number you will also be able to select a telephone number for PABX access.<br />

Sequential Dialling Attempts<br />

Sequential dialing is used by default and results in the reporting phone numbers programmed<br />

in the service being dialed sequentially. In the following example, a service is programmed<br />

with a two telephone numbers (Phone 1 and Phone 2) and a backup telephone number. The<br />

number of dialing attempts is set to 8 and the Use Alternate Dialing Method option is<br />

disabled.<br />

Success After 5 th Dialling Attempt With Phone Number 1<br />

In the following example, the <strong>Controller</strong> was able to communicate with the central station<br />

with the programmed phone number 1 on the 5th attempt.<br />

Dial<br />

Attempt Phone Number Dialed<br />

Result<br />

Number<br />

1 Phone Number 1 Fail<br />

2 Phone Number 1 Fail<br />

3 Phone Number 1 Fail<br />

4 Phone Number 1 Fail<br />

5 Phone Number 1 Success (Report OK)<br />

Success After 1 st Dialling Attempt With Back Up Phone<br />

In the following example, the <strong>Controller</strong> was able to communicate with the central station<br />

only after the backup phone number was used. This resulted in the opening of the reporting<br />

failure trouble zone as a result of the reporting failure. This is subsequently sealed on the<br />

next valid report from the backup phone number.<br />