To modify the IP address use the keypad as explained in section Entering Decimal Numbers<br />

on Page 405. Press [ENTER] to save the Octet that is being entered and move to the next<br />

Octet or the next screen once all four have been completed.<br />

Secondary Port<br />

The Secondary port configures the reporting service with the remote port number to<br />

communicate on for the secondary IP. By using this information in connection with the<br />

secondary IP a specific route can be set for this connection.<br />

SV001 Primary<br />

port: 09647<br />

To modify the port configuration use the keypad as explained in section Entering Decimal<br />

Numbers on Page 405 and Press [ENTER] to save the modified data.<br />

Back Up Service<br />

A back up service can be programmed to allow the IP reporting functions to be backed up by<br />

a telephone dialer or similar. Using a back up service can be beneficial to allow link failures<br />

and internet access to be reported over an alternate connection.<br />

SV001 Back Up<br />

None<br />

Use the [1] and [3] keys to scroll the service selection and press [ENTER] to select the<br />

service to be used for back up. For more information about the list control data entry refer to<br />

the section List Control Data Entry on Page 406.<br />

Server Polling Time<br />

The polling time is set to schedule periodic connections with the server. The polling messages<br />

sent to the receiver will depend on the format. Some formats require that the polling time be<br />

set at both the controller and receivers, in this case ensure that this setting matches the<br />

setting provided by the central monitoring station company.<br />

SV001 Polling<br />

time: 120 secs<br />

Edit the polling time to a value of 10 to 255 seconds, any number below 10 will disable the<br />

polling being sent to the server. Use the keypad as explained in section Entering Decimal<br />

Numbers on Page 405 and press [ENTER].<br />

The polling time set will periodically send the polling message for the AlarmNZ IP<br />

and Patriot LS30 reporting formats a standard contact ID message with the code<br />

602 will be sent for area 00 and point 999. In some cases these are used only to<br />

reset a polling time and not generated as alarms in the Central Station.<br />

Report Fail PGM Output<br />

The report fail output is activated when a message is not successfully reported to the<br />

programmed server (and backup server). The PGM is deactivated when an acknowledge is<br />

received.<br />