SV001 Parity<br />

No Parity<br />

Use the [1] and [3] keys to scroll the communication parity options and press [ENTER] to<br />

select the parity displayed. For more information about the list control data entry refer to the<br />

section List Control Data Entry on Page 406.<br />

Data Options<br />

The data configure various communication settings that affect the operation of the Clipsal C-<br />

Bus Interface protocol.<br />

SV001 Data<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 – Log Communication Events<br />

Enabled the service will log communication events that occur on the C-Bus<br />

System to the event buffer. It is recommended this is only turned on for<br />

commissioning purposes as a large number of events can be generated.<br />

Disabled the communication events will not be logged.<br />

Option 2 – Log Communication Errors<br />

Enabled the service will log C-Bus Communication errors that occur which<br />

relate to the PCI not being present or not accepting commands.<br />

Disabled the errors will not be logged and requests that generate errors will<br />

be silently discarded.<br />

Option 3,4,5,6,7 and 8 - Reserved<br />

Reserved.<br />

Reserved.<br />

It is recommended not to enable/disable or modify the settings of reserved options.<br />

PCI Fail Time<br />

The PCI fail time allows a timer to be triggered on each successful request from the C-Bus<br />

Clipsal PCI Interface. When this timer expires the system will perform a check to see if the<br />

PCI is still present and then activate the fail PGM output if a response is not received.<br />

SV001 PCI fail<br />

time: 120 secs<br />

To modify the fail time (000 to 255, a setting of 000 will result in the default of 120 seconds<br />

being used), use the keypad as explained in section Entering Decimal Numbers on Page 405<br />

and press [ENTER].<br />

239 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>