defined by the SCADA system that is being connected to. The address is programmed in<br />

Hexadecimal and can not be 0x00 or 0xFF.<br />

SV001 Device<br />

address: 01<br />

Type the appropriate 2 digit device address, after each digit you must press [] and [] to<br />

move to the next digit. When the desired device address is entered, press [ENTER] to save<br />

the programmed setting and move to the next screen. For more information about<br />

hexadecimal data entry refer to the section Hexadecimal Data Entry on Page 406.<br />

The device address must be configured for a value below 0xFF and above 0x00,<br />

failure to configure the address to an appropriate value will cause the system not to<br />

respond. Duplicate address will cause communication failures with the ModBUS<br />

Master application.<br />

Data Options<br />

The data configure various communication settings that affect the operation of the ModBUS<br />

protocol.<br />

SV001 Data<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 – Log Comm Events<br />

Enabled the service log communication events that occur on the ModBUS<br />

system to the event buffer.<br />

Disabled the communication events will not be logged.<br />

Option 2 – Log Comm Errors<br />

Enabled the service log ModBUS Communication errors that occur which<br />

relate to the requests of certain objects and information outside the bounds<br />

of the interface.<br />

Disabled the errors will not be logged and requests that generate errors will<br />

be silently discarded.<br />

Option 3 – Reserved<br />

Reserved.<br />

Reserved.<br />

Option 4 – Reserved<br />

Reserved.<br />

Reserved.<br />

Option 5 – Remote Buffer View<br />

235 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>