used to report over a standard phone network using another service. When this timer expires<br />

the Fail To Poll PGM output will also be activated.<br />

SV001 Poll fail<br />

time: 120 secs<br />

To modify the poll fail time (000 to 255, a setting of 000 will result in the default of 120<br />

seconds being used), use the keypad as explained in section Entering Decimal Numbers on<br />

Page 405 and press [ENTER].<br />

Fail To Poll PGM Output<br />

The fail to poll PGM output is activated when the DVAC service poll fail timer expires and is<br />

deactivated when the DVAC service completes a valid communication. This PGM setting can<br />

be used to trigger an audible alarm or other indication that DVAC hard line communication<br />

has failed.<br />

SV001 Poll fail<br />

pgm: --000:00<br />

To modify the poll fail PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

ModBUS Slave Service<br />

The ModBUS Slave service has two functions, one of these is to allow remote access to the<br />

Protégé System <strong>Controller</strong> from an Industrial Process Control solution or SCADA (System<br />

Control and Data Acquisition) System, the other is to allow an Industrial Process, PLC or other<br />

device to generate reportable actions within the Protégé System <strong>Controller</strong> (Zone Activation)<br />

making reporting of plant and equipment alarms a very simple process.<br />

To program the ModBUS slave service ensure that the service that has been selected is<br />

halted. Press the [ENTER] key until the display shows the service type selection screen.<br />

SV001 Ser Type<br />

ModBUS (Slave)<br />

Use the [1] and [3] keys to scroll the service types until you reach the ModBUS slave<br />

selection and press [ENTER] to select the ModBUS slave type displayed and proceed to the<br />

next programmable option for the ModBUS slave service. For more information about the list<br />

control data entry refer to the section List Control Data Entry on Page 406.<br />

The ModBUS Slave Service may require the RS232 serial interface to be converted<br />

from a RS485 Signal. Ensure the correct interface is used when interfacing to the<br />

Protégé System <strong>Controller</strong> and <strong>PRT</strong>-COMM. Refer to the communication <strong>PRT</strong>-COMM<br />

installation manual and ACC-485-ISO documentation.<br />

Service Mode<br />

The service mode determines how this service operates with the system controller. By default<br />

a service is set to start with the operating system. Setting a service to "Start With The<br />

Operating System" (Start With O/S) allows the service to operate automatically, if the system<br />

233 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>