Option 2 - DTMF Tone / Pulse Dialing<br />

Enabled the dialer will use pulse dialing to dial out.<br />

Disabled the dialer will always use DTMF to dial except when Option 3 has<br />

been enabled.<br />

Option 3 - Switch Dialing To Pulse On 5 th Atempt<br />

Enabled the dialer will switch to the pulse dialing format on the 5 th attempt<br />

to dial the selected phone number.<br />

Disabled the dialer will always use DTMF to dial.<br />

Option 4 - Switch To Second Phone Line On Failure<br />

Enabled the dialer will switch the secondary phone line over and use this to<br />

dial if the first phone line fails or fails to communicate.<br />

Disabled the dialer will use the first phone line.<br />

Option 5 - PABX Requires Pause<br />

Enabled the dialer will insert a pause of 2.5 seconds after the PABX<br />

telephone number is dialled.<br />

Disabled the dialer will dial the numbers with a standard DTMF inter digit<br />

delay.<br />

Option 6, 7 and 8 - Reserved<br />

Reserved.<br />

Reserved.<br />

It is recommended not to enable/disable or modify the settings of reserved options.<br />

Events Options<br />

The events options allow you to filter the type of events that this contact ID service will send<br />

to the monitoring station.<br />

SV001 Events<br />

[123456--]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 - Report Opens<br />

Enabled the service will report opens (Disarming) for the areas that are part<br />

of the area group assigned. An area group of none will mean ALL areas will<br />

be sent using this service.<br />

Disabled the dialer will not report opens.<br />

Option 2 - Report Closes<br />

Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong><br />