a suitable schedule here. Using the unlock on late control option prevents the door unlocking<br />

on schedule until the first user access the door.<br />

DR001 Lock Sch<br />

None<br />

Use the [1] and [3] keys to scroll the unlock schedule selection and press [ENTER] to select<br />

the schedule displayed. For more information about the list control data entry refer to the<br />

section List Control Data Entry on Page 406.<br />

Unlock Time<br />

The unlock time determines how long the lock that controls the door will remain unlocked for<br />

when a user access's the door.<br />

DR001 Unlock<br />

time: 005 secs<br />

To modify the unlock time (000 to 255 Seconds), use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER]. Setting a 000 value will result in<br />

the door not unlocking when a users access's the door.<br />

Pre-Alarm Time<br />

The pre-alarm time is programmed to allow the door to be left open for a certain period<br />

before it will generate a pre-alarm condition. When the pre-alarm condition is reached this will<br />

typically activate a PGM on the <strong>PRT</strong>-RDI2 that is controlling the door.<br />

DR001 Pre-Alarm<br />

time: 030 secs<br />

To modify the pre-alarm time (000 to 255 Seconds), use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER]. Setting a 000 value will result in<br />

the pre-alarm feature not operating.<br />

Maximum Door Open Time<br />

The maximum door open time when it is reached will generate a door left open alarm<br />

activating the appropriate trouble zone and PGM output on the <strong>PRT</strong>-RDI2 that is controlling<br />

the door.<br />

The default configuration will mean that the door will generate a left open alarm 15 seconds<br />

after the pre-alarm condition. For the trouble zones to activate they must be set in the reader<br />

expander.<br />

DR001 Max Open<br />

time: 045 secs<br />

To modify the maximum door open time (000 to 255 Seconds), use the keypad as explained<br />

in section Entering Decimal Numbers on Page 405 and press [ENTER].<br />