Table 2 - Normal Arm Schedule Example Programming<br />

If the area is armed before 1715 an Early to Arm event will be generated when the area is<br />

armed. At 1745 if the area is not armed the system will generate a Late to Arm event.<br />

AR001 Nor Arm<br />

None<br />

Use the [1] and [3] keys to scroll the schedule selection and press [ENTER] to select the schedule<br />

displayed. For more information about the list control data entry refer to the section List Control Data<br />

Entry on Page 406.<br />

Area Miscellaneous Options<br />

Miscellaneous options for the area include the settings for the restore on bell, child area<br />

operations, zone forcing and loiter mode control.<br />

AR001 Misc<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 - Restore Zones After Bell Time<br />

Enabled the zones that are assigned to this area will restore when the bell<br />

time completes. This does not prevent the zone from generating multiple<br />

alarms for another area this setting is specific to the area assigned.<br />

The zones in the area will still log an event regardless of the bell time to<br />

prevent a zone from triggering an event remove the event log option in the<br />

zone configuration.<br />

Setting this option will PREVENT the retrigger bell timer from<br />

operating in the zone type, do not use this option for an area that is<br />

used for automation control or motion controlled lighting.<br />

Disabled the zones for the bell will restore each time the zone restores.<br />

Option 2 - Rearm Area If Disarmed<br />

When enabled the area will re-arm if the area is disarmed. This feature is<br />

used for dead man timers and areas that should not remain disarmed for a<br />

longer than a predefined time.<br />

For this option to operate the re-arm time must be set to a value<br />

greater than 0.<br />

Disabled the re-arm operation will not function.<br />

Option 3 - Arm Child Area<br />

Enabled the child area will be armed when the parent (this) area is armed.<br />

Please refer option 4 as this will determine when the area is armed.<br />

165 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>