AR001 Count<br />

time: 000 on<br />

To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in<br />

section Entering Decimal Numbers on Page 405 and press [ENTER]. Both the on and off pulse<br />

settings must have a value greater than 000 for this feature to operate.<br />

Count PGM Pulse OFF Time<br />

The count PGM pulse off time is used to make the PGM output pulse on and off when<br />

activated. The value entered here must be greater than 0 and is in increments of 100ms. For<br />

example setting 10 will pulse the unit off for 1 second and then on for the programmed time<br />

set in the pulse on section.<br />

AR001 Count<br />

time: 000 off<br />

To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in<br />

section Entering Decimal Numbers on Page 405 and press [ENTER]. Both the on and off pulse<br />

settings must have a value greater than 000 for this feature to operate.<br />

Defer PGM or PGM Group<br />

You can assign a PGM or PGM group to activate whenever the area begins the defer warning<br />

cycle and is about to arm. The defer warning time is programmed in the defer time setting.<br />

The defer PGM or PGM Group will be deactivated when the area begins the arming cycle or<br />

when the defer time is cancelled by a user.<br />

AR001 Defer arm<br />

pgm: --000:00<br />

To modify the Defer PGM or PGM Group, use the settings as explained in section Entering PGM<br />

and PGM Groups on Page 410.<br />

Defer PGM Pulse ON Time<br />

The defer PGM pulse on time is used to make the PGM output pulse on and off when<br />

activated. The value entered here must be greater than 0 and is in increments of 100ms. For<br />

example setting 10 will pulse the unit on for 1 second and then off for the programmed time<br />

set in the pulse off section.<br />

AR001 Defer arm<br />

time: 000 on<br />

To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in<br />

section Entering Decimal Numbers on Page 405 and press [ENTER]. Both the on and off pulse<br />

settings must have a value greater than 000 for this feature to operate.<br />

Defer PGM Pulse OFF Time<br />

The defer PGM pulse off time is used to make the PGM output pulse on and off when<br />

activated. The value entered here must be greater than 0 and is in increments of 100ms. For<br />

example setting 10 will pulse the unit off for 1 second and then on for the programmed time<br />

set in the pulse on section.<br />