Recent Close Time<br />

The recent closing time defines how long the system considers an armed area recently closed.<br />

If, after arming the area, an alarm is generated within the programmed period, the Protégé<br />

System <strong>Controller</strong> transmits a recent closed message. For this feature to operate correctly the<br />

zone must have its report options enabled in the assigned zone type.<br />

AR001 Recent cls<br />

time: 000 secs<br />

To enter a recent closing delay time (000 to 250 minutes), use the keypad as explained in<br />

section Entering Decimal Numbers on Page 405 and press [ENTER]. Setting a value of 000<br />

will result in no recent closing reports being sent for the area.<br />

Disarm Delay Time<br />

The disarm delay time is used in conjunction with the Automatic Teller Machine control and<br />

banking control functions. Setting a disarm delay time will cause the area to delay by the<br />

programmed delay time any access to the area.<br />

AR001 Disarm dly<br />

time: 000 mins<br />

To enter a disarm delay time (000 to 250 minutes), use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER].<br />

Code Delay Time<br />

The code delay time is used in conjunction with the Automatic Teller Machine control and<br />

banking control functions. Setting a code delay time will cause the area to wait for a code for<br />

the delay by the programmed time.<br />

AR001 Code dly<br />

time: 000 secs<br />

To enter a code delay time (000 to 250 seconds), use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER].<br />

Maximum Bypass Count<br />

The bypass count number sets the maximum number of zones that can be bypassed within<br />

the programmed area.<br />

AR001 Bypass<br />

count: 000<br />

To enter a bypass count (000 to 250), use the keypad as explained in section Entering<br />

Decimal Numbers on Page 405 and press [ENTER].<br />

Maximum User Count<br />

The user count defines the maximum number of users that can be in the area at any one<br />

time. For example, if the user count is set to 10, then the 11th user who attempts to enter<br />

the area is denied access. Typically, the user count feature is used when an area is controlled<br />

by an entry and an exit reader. When an access control card is presented to exit the area, the<br />

153 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>