Automation Control Point<br />

An automation control point allows this zone type to control an automation point in response<br />

to a zone opening or closing. An automation point can be assigned to many different functions<br />

such as gardening irrigation, lighting circuits, CBus Circuits and any PGM Output. You must<br />

configure the appropriate options to trigger the Automation point.<br />

ZT001 Automate<br />

None<br />

Use the [1] and [3] keys to scroll the available automation points and press [ENTER] to<br />

select the automation point displayed. For more information about the list control data entry<br />

refer to the section List Control Data Entry on Page 406.<br />

Zone Type Alarm Options<br />

Alarm options for the zone type configure the operation of the zone type when an alarm,<br />

restore and tamper are generated.<br />

ZT001 Alarm<br />

[12345---]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 - Process Alarms<br />

Enabled the zone type will process alarms from the zone that it is assigned.<br />

Disabled the zone type will perform no function on an alarm being<br />

generated.<br />

Option 2 - Process Tamper 24HR Alarm<br />

Enabled the zone type will process tamper alarms from the zone that it is<br />

assigned.<br />

Disabled the zone type will perform no tamper processing.<br />

Option 3 - Entry Delay<br />

Enabled the zone type will start an entry delay timer for the assigned area<br />

when the zone generates an alarm.<br />

Disabled the zone type will not perform any entry delay actions.<br />

Option 4 - Entry Delay Follow<br />

Enabled the zone type will allow this zone to generate alarms during the<br />

entry delay however it will generate an alarm if the alarm condition occurs<br />

outside the entry delay period.<br />

Disabled the zone type operates normally.<br />

Option 5 - Exit Delay Follow<br />

Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong><br />