Option 2 – Channel Input Output Configuration<br />

When the option is enabled the input or output will operate in Current Mode<br />

and use the 0-20mA and 4-20mA interface.<br />

Disabled the channel will operate in 0-10V input or output mode.<br />

Option 3 – Preset <strong>PRT</strong>-DAC4 Output on Power Up<br />

Enabled and the analog expansion module is a DAC module the output will<br />

be preset when it powers up to the setting in option 4.<br />

Disabled the DAC output will be set to the last known value that it received.<br />

Option 4 – Set to Full Scale Output<br />

Enabled and option 3 enabled the DAC output will be set to the maximum or<br />

full scale deflection.<br />

Disabled and option 3 enabled the DAC will output a analog value of 0 on<br />

the voltage or current outputs.<br />

Option 5 – Reserved Do Not Modify.<br />

Option 6 – Differentiate On Send Operation<br />

Enabled the Analog Input channel will constantly monitor the analog input<br />

value for any variance greater than the configured differentiate value set for<br />

the channel and then send an update to the system controller.<br />

Disabled the Input Channel will be sent based on the period configured in<br />

the channel time setting.<br />

Option 7 – Log Raw Analog Data<br />

Enabled the Analog Expander channels when updated either as an input or<br />

an output will trigger a log in the event screen with the exact raw value.<br />

This is ideal for fault finding HOWEVER should not be left on in a live system<br />

as it will fill the event review rapidly.<br />

To log data from a channel for charting and display purposes utilize<br />

the log option for variables in the Protégé System Management<br />

Suite.<br />

Disabled the data is not logged to the review screen.<br />

Option 8 - Reserved<br />

Reserved.<br />

Reserved.<br />

It is recommended not to enable/disable or modify the settings of reserved options.<br />

Analog Channel 1 Update Time<br />

When the analog input expander is used the channel will generate analog information that is<br />

stored in the variable associated with the analog expander. The data can be programmed to<br />