Disabled bond sensing will operate normally.<br />

Option 4 - Invert Request to Exit Input<br />

Enabled the reader will invert the request to exit input.<br />

Disabled REX input will operate normally.<br />

Option 5 - Invert Request to Enter Input<br />

Enabled the reader will invert the request to enter input.<br />

Disabled REN input will operate normally.<br />

Option 6 - Request To Exit Operates Always<br />

Enabled the reader will always allow a request to exit event EVEN if the door<br />

is forced open. This will not restart the forced door or the door alarm<br />

operation.<br />

Disabled REX input will operate only when the door is closed.<br />

Option 7 - Recycle Door Open Too Long Timer On Request To Exit Operation<br />

Enabled the reader will extend the door open time when the REX is<br />

received. The REX must be received during the normal open time or during<br />

the pre-alarm time for the timer to be recycled. Pressing the request to exit<br />

once the door open too long has been entered will require the door to be<br />

closed. This option will not affect the ability for the request to exit action to<br />

unlock the door.<br />

Disabled REX input will not alter the door open time once the door as been<br />

opened.<br />

Option 8 - Reserved<br />

Reserved.<br />

Reserved.<br />

It is recommended not to enable/disable or modify the settings of reserved options.<br />

Reader Port 2 Process Options<br />

Options that relate to the extra reader functions.<br />

RD001 R2 Process<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 – Convert Force to Door Open<br />

Enabled the reader expander will process door forced open events as door<br />

open events.<br />

Disabled the reader will process forced door events as normal.<br />

113 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>