Reader Port 1 Elevator Options<br />

Options that relate to the elevator functions.<br />

RD001 R1 Elv Opt<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 – Invert Floor Relays<br />

Enabled the reader expander will invert all the relays on the PX16’s<br />

connected that are used for elevator control.<br />

Disabled the reader will not invert the relays.<br />

Option 2 – Control on Comm Fail<br />

Enabled the PX16 used for elevator control will control the state of the<br />

relays when they go offline. Option 3 determines the state the relays will<br />

go into.<br />

Disabled the PX16 used for elevator control will not change the state of the<br />

relays when they go offline..<br />

Option 3 – Activate on Comm Fail<br />

Enabled the PX16 will activate the relays when they go offline.<br />

Disabled the PX16’s will deactivate the relays when they go offline.<br />

Option 4 - 8 - Reserved<br />

Reserved.<br />

Reserved.<br />

Reader Port 1 Function PGM<br />

You can assign a PGM or PGM group that is used by the multiple badge options.<br />

RD001 R1 Func<br />

pgm: --000:00<br />

To modify the PGM or PGM Group, use the settings as explained in section Entering PGM and<br />

PGM Groups on Page 410.<br />

Reader Port 2 Mode<br />

The reader mode setting determines what function the reader attached to port two will<br />

perform.<br />

105 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>