It is recommended not to enable/disable or modify the settings of reserved options.<br />

Reader Port 1 Process Options<br />

Options that relate to the extra reader functions.<br />

RD001 R1 Process<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 – Convert Force to Door Open<br />

Enabled the reader expander will process door forced open events as door<br />

open events.<br />

Disabled the reader will process forced door events as normal.<br />

Option 2 – Disable Red LED Processing<br />

Enabled the reader expander will not control the Red LED (L2) and the PGM<br />

can be used for another function, this is particularly useful if the attached<br />

proximity reader LED’s is controlled with one wire.<br />

Disabled the reader will turn on the Red LED when the door is locked.<br />

Option 3 – Disable Green LED Processing<br />

Enabled the reader expander will not control the Green LED (L1) and the<br />

PGM can be used for another function, this is particularly useful if the<br />

attached proximity reader LED’s is controlled with one wire.<br />

Disabled the reader will turn on the Green LED when the door is unlocked.<br />

Option 4 – Disable Buzzer Processing<br />

Enabled the reader expander will not control the Buzzer Output (BZ) and<br />

the PGM can be used for another function.<br />

Disabled the reader will control the buzzer output.<br />

Option 5 – Recycle REX time<br />

Enabled the the Reqest to Exit timer will always be reloaded when the<br />

Reqest to Exit input is closed. This means that the door can be opened for<br />

the door unlock time after the Reqest to Exit input has closed even if the<br />

Door lock is not activated.<br />

Disabled the door does not reload the Reqest to Exit time while the door is<br />

open.<br />

Option 6 - 8 - Reserved<br />

Reserved.<br />

Reserved.<br />

Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong><br />

104