Disabled the reader performs no action when a card is presented and the<br />

door is unlocked or open.<br />

Option 2 - Send Door Monitoring Events<br />

Enabled the reader will send door events when the door input is opened or<br />

closed. This is enabled by default but should be disabled on at least one<br />

reader port if both reader ports are controlling the same door (ENTRY and<br />

EXIT access control).<br />

Disabled the reader expander will not send any door events.<br />

Option 3 - LED Follow Lock Status<br />

Enabled the reader will activate the LED outputs on the reader expander<br />

when the lock is opened. This option DOES not prevent the outputs from<br />

being used to display the area armed or alarm status.<br />

Disabled the reader will not perform any function on the LED outputs.<br />

Option 4 - Bond Sense Input Enable<br />

Enabled the magnetic bond sense functions. The magnetic bond sense is a<br />

contact that indicates if the magnetic bond between the electromagnet and<br />

the clamp is complete. It is used when a separate door contact and bond<br />

sense input are to be used however the generation of door events should be<br />

processed using both inputs.<br />

When opening either of the two contacts open (Door Contact or Bond Sense<br />

Input) the door monitoring will see this as the door being opened and<br />

process it accordingly.<br />

Disabled the reader will not include the bond sense input in the door status<br />

processing.<br />

Option 5 - Request To Exit (REX) Enabled<br />

Enabled the reader expander will generate request to exit events from the<br />

REX input on the reader expander.<br />

Disabled the keypad will not generate any REX events.<br />

Option 6 - Request To Enter (REN) Enabled<br />

Enabled the reader expander will generate request to enter events from the<br />

REN input on the reader expander.<br />

Disabled no action will be taken for the Request To Enter function.<br />

Option 7 - Generate Format Error Events<br />

Enabled the reader expander will send a detailed format error to the system<br />

controller if it receives information from the reader that does not comply<br />

with the programmed format. Format errors include bit count, byte count,<br />

parity, checksum and LRC calculation failures.<br />

Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong><br />