MODEL 3000 / ACCESS 4000 Programmer’s Manual - <strong>Doors</strong>. Rev 4.50 [MENU 7-6] p 3<br />

e.g.<br />

-Lock Open Time of “5”, will activate the Lock Aux. for 500 mS. ( 5 x 100mS)<br />

-Lock Open Time of “50”, will activate the Lock Aux. for 5 Sec. ( 50 x 100mS)<br />

This is done by setting Switch 8 on DIPswitch 2 to the ON position.<br />

When set, the Lock Open Time will then be processed as 100 milli-Second<br />

increments for all 4 <strong>Doors</strong> on that particular Module.<br />

See the Intelligent 4 Door Access Module installation manual for location of<br />

DIPswitch.<br />

Only Modules with the DIPswitch set to ON will process the Lock Open Time in<br />

this way. Any other Modules with the DIPswitch left in the OFF position, will<br />

process the Lock Open Time in the normal manner as 1 second increments.<br />

D001 Max. Open<br />

Time: 030 sec<br />

This screen determines the maximum time this Door may be left open before creating<br />

a “Door Open Too Long” (Door Held Open) alarm. The “Door Open Too Long”<br />

alarm is a System Input generated from the LCD Terminal or Reader Module<br />

associated with the Door. This time is programmable from 1 to 255 seconds.<br />

Note: In earlier 2 Door Reader Modules (Part no: 993012) configured for “2” Door<br />

mode, the “Maximum Door Open Time” set for the 1st Door on the Module was<br />

utilized as the Max. Door Open Time for both <strong>Doors</strong>.<br />

All current Access Modules allow the Max. Door Open time to be defined and<br />

operate separately for each Door.<br />

i.e. 995012-2 Door Access Modules and Intelligent 4 Door Access Modules.<br />

D001 E.......<br />

Opts -> nnnnnnnn<br />

This screen allows the Installer to programme various Door options.<br />

E<br />

Extra Area Counting<br />

This option allows the User count in the User’s “Extra Area” to be incremented/<br />

decremented when the User is granted access through this door.<br />

If the reader is on the “Outside”, the User count is incremented in the User’s Extra<br />

Area.<br />

6. <strong>Doors</strong><br />

If the reader is on the “Inside”, the User count is decremented in the User’s Extra<br />

Area.<br />

No “count” or “Arm on count = 0” will occur on the Door Areas when this option<br />

is enabled.<br />

. Spare<br />

Spare for future use. This option must be set to “n”.<br />

Copyright exists on this manual. Unauthorised copying of this document is prohibited.