IQ Quick Programming Guide V3.604 - Security Help Desk
IQ Quick Programming Guide V3.604 - Security Help Desk
IQ Quick Programming Guide V3.604 - Security Help Desk
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
INNER RANGE <strong>IQ</strong> PLUS. <strong>Quick</strong> Programmer’s Manual.<br />
Version 3.604 (31/03/05) p23<br />
No Access Options.<br />
Go to Step 34<br />
“Change Installer PIN”<br />
▼<br />
31. REX BUTTON ON TERMINAL<br />
An Installer Code or Master User Code must be used to program this option<br />
1) Key in your PIN, then Press , , , , then to enable ( to disable ), default is disabled<br />
This option enables the OFF key on the Terminal to act as a REX button<br />
▼<br />
32. DOOR FORCED<br />
An Installer Code or Master User Code must be used to program this option<br />
<strong>Programming</strong> the DOOR FORCED system input for DOOR 1, to operate an auxiliary.<br />
This option can require the use of the plug-on auxiliary board<br />
1) Key in your PIN, then Press , , , , then , , then<br />
This assigns event type 131 to Aux 10, when the door reed for DOOR1 goes into alarm without a valid request to<br />
open the door, an output on auxiliary 10 will occur. Cleared with a valid PIN + OFF key.<br />
▼<br />
33. DOOR OPEN TOO LONG (DOTL)<br />
An Installer Code or Master User Code must be used to program this option<br />
<strong>Programming</strong> the DOTL system input for DOOR 1, to operate an auxiliary.<br />
This option can require the use of the plug-on auxiliary board<br />
1) Key in your PIN, then Press , , , then , , then<br />
This assigns event type 141 to Aux 9, when the door reed for DOOR1 is open for longer than a period of time<br />
equal to 4 times that of the lock open time set at address 909. Cleared with a valid PIN + OFF key or valid card badge.<br />
▼<br />
▼