<strong>MV</strong> SERIES<br />

CUBERS<br />

TECHNICAL SERVICE TRAINING<br />

Welcome to another <strong>Scotsman</strong> technical service presentation. This<br />

one will cover the NEW <strong>MV</strong> Series Modular Ice Cube Machines<br />

models <strong>MV</strong> <strong>306</strong>, <strong>MV</strong> <strong>456</strong> , <strong>MV</strong> <strong>606</strong>, <strong>MV</strong> <strong>806</strong> and <strong>MV</strong> <strong>1006</strong>.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

TOPICS<br />

On the next slides are shown the following steps by steps<br />

procedures:<br />

• UNPACKING<br />

• INSTALLATION<br />

• START UP AND OPERATIONAL CHECKS<br />

• OPERATING PRINCIPLES and COMPONENTS<br />

• MAINTENANCE<br />

• SERVICE ANALYSIS


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

UNPACKING


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

UNPACKING<br />

The machines are<br />

supplied in a carton box<br />

secured by two plastic<br />

strips to a wooden base.<br />

Check first the outside<br />

conditions of carton box<br />

and wooden base then cut<br />

the two plastic strips,<br />

remove the tape and then<br />

the carton box. <strong>MV</strong> <strong>306</strong>


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

UNPACKING<br />

<strong>MV</strong> <strong>456</strong>-<strong>606</strong><br />

<strong>606</strong>-<strong>806</strong>-<strong>1006</strong>


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

Visually inspect the<br />

exterior of the machine<br />

then remove the front<br />

panel…. ………<br />

UNPACKING<br />

……..and<br />

the two<br />

side<br />

panels …..


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

Remove the<br />

water inlet<br />

and outlet<br />

hoses as well<br />

as……..<br />

UNPACKING


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

UNPACKING<br />

……….the air<br />

baffle on the<br />

air cooled<br />

version.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

UNPACKING<br />

Unscrew the<br />

unit frame<br />

from the<br />

wooden<br />

base….


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

UNPACKING<br />

The Modular Cuber machines<br />

require for the installation the use of<br />

a companion storage bin to store the<br />

ice produced.<br />

Storage bins required are:<br />

• B 193 for <strong>MV</strong> <strong>306</strong><br />

• B 393 for <strong>MV</strong> <strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<br />

<strong>1006</strong><br />

B 193


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

UNPACKING<br />

Unpack the<br />

storage bin and<br />

visually inspect<br />

the exterior then<br />

remove from<br />

the inside the<br />

carton box<br />

containing the<br />

legs as well as<br />

the drain hose<br />

and the plastic<br />

scoop.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

On B 193/393<br />

Storage Bin<br />

install the four<br />

legs and their<br />

adjusting<br />

leveling nuts on<br />

the bottom base.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

Place the<br />

storage bin in its<br />

definitive<br />

location then<br />

install on top of<br />

its upper side<br />

the rubber<br />

gasket then….


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

…...install on top of<br />

the same the ice<br />

machine and secure<br />

it with the two<br />

screws.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

Remove the<br />

plastic tape<br />

securing the<br />

plastic cover<br />

to the vertical<br />

evaporator<br />

then….


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

…..push the<br />

right side of<br />

the front<br />

plastic cover...


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

…..and take it<br />

out.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

Take out the<br />

adhesive tape<br />

holding the<br />

Ice Thickness<br />

Sensor to the<br />

front cells of<br />

the evaporator<br />

then re-install<br />

the plastic<br />

cover.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

On air cooled<br />

version<br />

unloose a little<br />

bit the three<br />

screws<br />

securing the<br />

air cooled<br />

condenser to<br />

the unit<br />

frame….<br />

INSTALLATION


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

…. and install<br />

the metal plate<br />

(air baffle) on<br />

the back side<br />

of the<br />

machine so….


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

…. to<br />

minimize the<br />

possible<br />

recycling of<br />

hot air<br />

through the<br />

left side<br />

lowered panel.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

The installation of the<br />

metal plate (air<br />

separator) grants also a<br />

minimum distance<br />

between the back side of<br />

the machine and the wall<br />

so to assure a correct and<br />

adequate ventilation.<br />

TOP VIEW<br />

MINIMUM<br />

DISTANCE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

Check the data<br />

plate of the<br />

machine located on<br />

the rear panel for<br />

correct voltage as<br />

well as for the<br />

proper wiring/fuse<br />

size.<br />

Remember that all<br />

machines require a<br />

solid earth wire.<br />

INSTALLATION


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

Check for the correct water and ambient conditions that should be:<br />

• Min. ambient temperature<br />

• Max. ambient temperature<br />

• Min. water temperature<br />

• Max. water temperature<br />

• Min. water pressure<br />

• Max. water pressure<br />

10ºC (50F)<br />

40ºC (100F)<br />

5ºC (40F)<br />

35ºC (90F)<br />

1 bar (14 PSI)<br />

5 bar (70 PSI)


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

Adequate<br />

space must left<br />

for proper<br />

water and<br />

electrical<br />

connections on<br />

the rear side of<br />

the machine<br />

and a<br />

minimum<br />

clearance of 15<br />

cm on right<br />

side for best<br />

routing air.<br />

Min. space 15 cm


<strong>MV</strong> <strong>306</strong><br />

INSTALLATION - AIR CIRCULATION<br />

COLD AIR<br />

FAN MOTOR<br />

CONDENSER<br />

HOT AIR<br />

COMPRESSOR<br />

EVAPORATOR<br />

ICE CHUTE<br />

OPENING


<strong>MV</strong> <strong>456</strong>-<strong>606</strong><br />

<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION - AIR CIRCULATION<br />

FAN MOTOR<br />

COLD AIR<br />

CONDENSER<br />

HOT AIR<br />

COMPRESSOR<br />

EVAPORATOR<br />

ICE CHUTE<br />

OPENING


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION<br />

Level the unit<br />

on both<br />

directions front<br />

to rear and<br />

right to left<br />

side using the<br />

adjustable<br />

legs.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION - ELECTRICAL<br />

Install, on the cable supply<br />

with the machine, an<br />

adaguate electrical plug<br />

according to the local<br />

standards and regulations.<br />

Maximum voltage variation<br />

should be ±10%.<br />

Machine must be<br />

individually fuse protected.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION - WATER IN<br />

Connect the water inlet 3/4”<br />

male threat of the water inlet<br />

fitting to the water supply line<br />

by means of the rubber hose<br />

provided with machine.<br />

Install on water supply line<br />

closed to the machine a water<br />

valve (tap).


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

INSTALLATION - WATER DRAIN<br />

Connect the 20<br />

mm O.D. fitting<br />

of the water drain<br />

with the flexible<br />

hose supply with<br />

the machine with<br />

its proper clamp.<br />

As water will be<br />

mainly drained<br />

under pressure<br />

(by water pump)<br />

it is not necessary<br />

to have a vented<br />

drain.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

TYPICAL INSTALLATION<br />

AIR COOLED<br />

POWER<br />

HAND DISCONNECT<br />

SWITCH<br />

WATER INLET<br />

WATER<br />

VALVE<br />

WATER DRAIN<br />

WATER<br />

FILTER<br />

WATER DRAIN


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

TYPICAL INSTALLATION<br />

WATER COOLED<br />

POWER<br />

HAND DISCONNECT<br />

SWITCH<br />

WATER INLET<br />

WATER<br />

VALVE<br />

WATER DRAIN<br />

WATER<br />

FILTER<br />

WATER DRAIN


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND<br />

OPERATIONAL<br />

CHECKS


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

• Open the<br />

water<br />

tap/valve.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

• Switch ON the<br />

power on the<br />

electrical supply<br />

line.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

The machine enter in the<br />

Start Up mode with the<br />

PC Board energized as<br />

well as the Green LED<br />

of the machine under<br />

power.<br />

The Green LED <br />

machine in operation is<br />

energized too, blinking<br />

fast for 40 seconds.<br />

of<br />

START UP


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP<br />

During the Start Up cycle the<br />

components in operation are:<br />

• Hot gas valve


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP<br />

During the Start<br />

Up cycle the<br />

components in<br />

operation are:<br />

• Hot gas valve<br />

• Water Drain<br />

Valve


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP<br />

During the Start Up<br />

cycle the components<br />

in operation are:<br />

• Hot gas valve<br />

• Water Drain Valve<br />

• Harvest assist<br />

solenoid


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP<br />

During the Start Up<br />

cycle the components<br />

in operation are:<br />

• Hot gas valve<br />

• Water Drain Valve<br />

• Harvest assist<br />

solenoid<br />

• Water pump


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP<br />

Start up cycle resuming chart<br />

Compressor<br />

Water Water inlet inlet valve valve<br />

Water Water pump pump<br />

Hot Hot gas gas valve valve<br />

Water Water drain drain valve valve<br />

Harvest assist assist sol. sol.<br />

0 40'' 40''


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

After the Start Up cycle the<br />

machine enters directly into the<br />

Freezing cycle with the<br />

following components<br />

energized:<br />

• Water Inlet Valve<br />

FREEZING CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

• Water Inlet Valve<br />

• Compressor<br />

FREEZING CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

• Water Inlet Valve<br />

• Compressor<br />

• Fan motor (in continuous<br />

operation for the first 3<br />

minutes)<br />

FREEZING CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

The LED energized are:<br />

• Machine under power<br />

FREEZING CYCLE<br />

• Machine in operation (steady)<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

FREEZING CYCLE<br />

Water, coming<br />

through the Water<br />

Inlet Solenoid<br />

Valve....


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

FREEZING CYCLE<br />

…..fill up the<br />

water reservoir...


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

….till the maximum level….<br />

FREEZING CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

FREEZING CYCLE<br />

….controlled by the<br />

shortest metal pin of the<br />

Water Level Sensor.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

FREEZING CYCLE<br />

30 seconds later,<br />

the Water Pump<br />

starts up.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

In the meantime<br />

the condenser<br />

sensor starts to<br />

transmit the current<br />

to the PC<br />

Board…..<br />

FREEZING CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

…. keeping in<br />

operation the Fan<br />

Motor in ON-OFF<br />

mode according to<br />

the condenser<br />

temperature.<br />

FREEZING CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

FREEZING CYCLE<br />

The machine remains in<br />

the freezing cycle with the<br />

ice that become thicker ….


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

……till the two<br />

metal plates of<br />

the Ice<br />

Thickness<br />

Sensor are<br />

covered by the<br />

water cascading<br />

down through<br />

the front surface<br />

of the ice plate.<br />

FREEZING CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

When the<br />

Power is<br />

transmitted back<br />

continuously to<br />

the PC Board<br />

through the<br />

metal plates of<br />

the Ice<br />

Thickness<br />

Sensor for more<br />

then 6 seconds,<br />

the….<br />

FREEZING CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

FREEZING CYCLE<br />

….machine enters in the Pre-Harvest first or directly into the<br />

Harvest Cycle mode according to:<br />

FAN MOTOR IN ON-OFF MODE<br />

DURING THE PREVIOUS<br />

FREEZING CYCLE<br />

RISE UP THE CUT IN<br />

TEMPERATURE OF THE<br />

CONDENSER SENSOR TO 38°C AND<br />

EXTEND THE LENGTH OF<br />

FREEZING CYCLE BY 30" MORE<br />

THEN GO INTO HARVEST CYCLE<br />

FAN MOTOR ALWAYS IN ON<br />

MODE DURING THE PREVIOUS<br />

FREEZING CYCLE<br />

GO STRAIGHT TO THE HARVEST<br />

CYCLE<br />

FAN MOTOR OFF


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

FREEZING CYCLE<br />

Freezing cycle resuming chart<br />

Compressor<br />

Water Water inlet inlet valve valve<br />

Water Water pump pump 30" 30"<br />

Fan Fan motor motor < 30°C 30°C 3' 3'<br />

30" 30"<br />

Fan Fan motor motor > 30°C 30°C<br />

0 20' 20'


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

WATER SYSTEM - FREEZE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

During the harvest cycle the<br />

components in operation are:<br />

• Hot Gas valve<br />

HARVEST CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

• Hot Gas valve<br />

•Water<br />

Drain/Purge<br />

Valve<br />

HARVEST CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

• Hot Gas valve<br />

•Water<br />

Drain/Purge<br />

Valve<br />

• Harvest assist<br />

solenoid<br />

HARVEST CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

• Hot Gas valve<br />

•Water<br />

Drain/Purge Valve<br />

• Harvest assist<br />

solenoid<br />

•Water Pump for<br />

the first 6”<br />

HARVEST CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

• Hot Gas valve<br />

• Water Drain/Purge Valve<br />

• Harvest assist solenoid<br />

•Water Pump for the first 6”<br />

• Compressor<br />

HARVEST CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

• Hot Gas valve<br />

HARVEST CYCLE<br />

• Water Drain/Purge Valve<br />

• Harvest assist solenoid<br />

• Water Pump for the first 40”<br />

• Compressor<br />

and both LEDs<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET<br />

• Machine Under Power<br />

• Machine in Operation


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

HARVEST CYCLE<br />

The Fan Motor remains<br />

in OFF mode unless the<br />

Condenser Sensor<br />

probe rises up to more<br />

then 38°C (same set up<br />

as per end of freezing<br />

cycle).


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

While the ice plate is<br />

falling down, it moves<br />

the front plastic cover<br />

out from the evaporator<br />

causing the activation<br />

of the magnetic switch<br />

to restart a new<br />

freezing cycle.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

HARVEST CYCLE<br />

Harvest cycle resuming chart<br />

Compressor<br />

Water inlet valve<br />

Water pump 6"<br />

Hot gas valve<br />

Water drain valve<br />

Harvest assist sol.<br />

0 END HARVEST CYCLE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

WATER SYSTEM - HARVEST<br />

1ST PART - 6”<br />

ON


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

WATER SYSTEM - HARVEST<br />

2ND PART - TO THE END OF HARVEST CYCLE<br />

OFF


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

OPERATING PRINCIPLES - BIN FULL<br />

When the last ice plate<br />

discharged from the<br />

evaporator doesn’t find<br />

any more space into the<br />

storage bin it remains in<br />

between the storage bin<br />

and the machine<br />

keeping…...


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

OPERATING PRINCIPLES - BIN FULL<br />

…….the plastic<br />

deflector/cover in open<br />

position.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

OPERATING PRINCIPLES - BIN FULL<br />

By doing so the magnet is<br />

kept far from its switch for<br />

more then few seconds that<br />

it is equivalent to transmit<br />

the signal to the PC Board<br />

of Bin Full.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

In case the magnetic sensor remains open, during freezing or<br />

harvest cycle, for more then 30 seconds, the machine stops its<br />

operation in Bin Full with the glowing of the BIN FULL<br />

YELLOW LED.<br />

BIN FULL<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

Both the last two Red<br />

LED are ON steady:<br />

ALARM CONDITIONS<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

Both the last two<br />

Red LED are ON<br />

STEADY:<br />

Condenser Sensor<br />

OUT OF ORDER


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

Both the last two Red<br />

LED are BLINKING<br />

SLOW:<br />

WATER ERROR<br />

ALARM CONDITIONS<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

Both the last two Red<br />

LED are BLINKING<br />

SLOW:<br />

WATER ERROR<br />

Water level inside the<br />

water sump too low<br />

after 3 minutes from<br />

the activation of the<br />

Water Inlet Valve.<br />

CORRECT<br />

WATER LEVEL<br />

TOO LOW<br />

WATER LEVEL


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

Both the last two Red<br />

LED are BLINKING<br />

FAST:<br />

ALARM CONDITIONS<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

Both the last two Red<br />

LED are BLINKING<br />

FAST:<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET<br />

RESET MODE<br />

Charging water through<br />

the Water Inlet Solenoid<br />

Valve after the tripping<br />

OFF on WATER ERROR


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

The fourth Red LED is<br />

BLINKING SLOW:<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

The fourth Red LED is<br />

BLINKING SLOW:<br />

TOO HI<br />

CONDENSING<br />

TEMPERATURE<br />

The condenser sensor<br />

detected a temperature<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

0<br />

> 65°C


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

The fourth Red LED is<br />

ALARM CONDITIONS<br />

BLINKING FAST:<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET<br />

RESET MODE<br />

Condenser Sensor < 50°C<br />

Fan motor in operation for 3<br />

minutes then back on Start<br />

Up Cycle Mode.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

The fourth Red LED is<br />

ON STEADY:<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

The fourth Red LED is<br />

ON STEADY:<br />

Too long Harvest Cycle > 3’ 30”<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

The fifth Red LED is<br />

ON STEADY:<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

The fifth Red LED is<br />

ON STEADY:<br />

TOO HI DISCHARGE<br />

PRESSURE > 33 bar 460 PSI<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

The fifth Red LED is<br />

ALARM CONDITIONS<br />

BLINKING FAST:<br />

RESET MODE<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET<br />

Push the Reset Button of the<br />

Pressure Control…..


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

The fifth Red LED is<br />

ALARM CONDITIONS<br />

BLINKING FAST:<br />

RESET MODE<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET<br />

First the fan motor starts up<br />

for 3 minutes then…... the<br />

entire machine through the<br />

Start Up Cycle Mode.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

The PC Board is also checking the maximum time of the freezing<br />

cycle that changes according to the operation of the fan motor<br />

during the freezing cycle (room temperature):<br />

• Fan motor in ON-OFF OFF mode:<br />

• Fan motor ON all the time:<br />

Max. freezing cycle length<br />

equal to 30 minutes<br />

Max. freezing cycle length<br />

equal to 40 minutes


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

Whenever the machine remains in the<br />

Freezing Cycle for the Maximum time (30<br />

or 40 minutes), the PC Board moves the<br />

unit directly into the Harvest Cycle.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

In case the Harvest Cycle takes longer<br />

then 3’ 30”, the machine trips OFF with<br />

the glowing of the fourth Red LED.<br />

POWER<br />

OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

To Restart the<br />

machine it is<br />

necessary to Push<br />

the RE-SET<br />

BUTTON


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

In case the Water Level Sensor<br />

ALARM CONDITIONS<br />

does NOT detect any presence of<br />

water, after the first 3 minutes of<br />

operation in the freezing cycle,<br />

the P C Board switches OFF the<br />

entire machine with the SLOW<br />

BLINKING of the last two RED<br />

LEDs (WATER ERROR).<br />

POWER OPER.<br />

BIN<br />

FULL<br />

ALARM<br />

ALARM<br />

HI<br />

PRESS.<br />

RE-SET


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

ALARM CONDITIONS<br />

WATER ERROR:<br />

The machine remains in OFF mode for 30’ then it tries to re-fill<br />

water: Water re-filled?<br />

YES:<br />

Machine remains in operation<br />

NO: Machine again in OFF mode for additional 30’


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

The components energized at<br />

beginning of the freezing cycle<br />

are:<br />

• PC Board


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

The components energized at<br />

beginning of the freezing cycle<br />

are:<br />

• PC Board<br />

• Contactor


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

The components energized at<br />

beginning of the freezing cycle<br />

are:<br />

• PC Board<br />

• Contactor<br />

• Compressor


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

Few seconds later, as soon<br />

as the discharge pressure<br />

reaches 17 bar (240 PSI),<br />

the fan motor starts to<br />

operate in ON-OFF mode<br />

keeping the discharge<br />

pressure between 15 and<br />

17 bar (210÷240 PSI).


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

The operation of the<br />

fan motor is<br />

controlled by a<br />

condenser<br />

temperature sensor<br />

located on the<br />

outlet of condenser<br />

that transmit a<br />

signal to the PC<br />

Board to activate in<br />

ON-OFF mode the<br />

fan motor.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

The Water Pump<br />

starts up 30<br />

seconds later so to<br />

allow the evaporator<br />

to freeze up its outside<br />

surface and reduce as<br />

much as possible the<br />

slush formation.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

While the water<br />

is falling dawn<br />

from the upper<br />

side of the<br />

evaporator it<br />

enter into the<br />

refrigerated<br />

cells starting the<br />

formation of a<br />

small layer of<br />

ice.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

The machine remains in<br />

the freezing cycle with the<br />

ice that become thicker ….


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

……till the two<br />

metal plates of<br />

the Ice<br />

Thickness<br />

Sensor are<br />

covered by the<br />

water falling<br />

dawn through<br />

the front surface<br />

of the ice plate.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

By doing so a<br />

low voltage<br />

current is<br />

supply back to<br />

the PC Board<br />

using water as a<br />

conductor.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

10 seconds later the PC<br />

Board put the machine<br />

in the harvest cycle<br />

energizing the:<br />

• Hot Gas Valve


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

10 seconds later<br />

the PC Board put<br />

the machine in<br />

the harvest cycle<br />

energizing the:<br />

• Hot Gas Valve<br />

• Water drain<br />

Valve


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

10 seconds later<br />

the PC Board put<br />

the machine in<br />

the harvest cycle<br />

energizing the:<br />

HARVEST CYCLE<br />

• Hot Gas Valve<br />

• Water drain<br />

Valve<br />

•Harvest<br />

Assist Valve


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

The other electrical<br />

components that<br />

remain energized<br />

during the harvest<br />

cycle are:<br />

• Compressor


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

……….and for the<br />

first 6’’ only the<br />

•Water Pump


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

The refrigerant in hot<br />

gas state, pumped by<br />

compressor, reaches the<br />

back side of the<br />

evaporator warming up<br />

its surface and partially<br />

melting the ice.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

After one-one and<br />

half minute from the<br />

beginning of the<br />

harvest cycle, the ice<br />

plate is moving out<br />

from the evaporator<br />

cells….


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

….falling down into the<br />

bottom storage bin.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

START UP AND OPERATIONAL CHECKS<br />

In the meantime also<br />

the water drain valve<br />

and the water pump<br />

are energized<br />

pumping out the<br />

water from the sump<br />

for the first 6” so to<br />

reduce as much as<br />

possible the<br />

accumulation of scale<br />

into the water system.


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

OPERATING<br />

PRINCIPLES<br />

and<br />

COMPONENTS


Compressor<br />

<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

OPERATING PRINCIPLES - FREEZE<br />

Evaporator<br />

Hot<br />

gas<br />

valve<br />

Air cooled<br />

condenser


Compressor<br />

<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

OPERATING PRINCIPLES - HARVEST<br />

Evaporator<br />

Hot<br />

gas<br />

valve<br />

Air cooled<br />

condenser


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

WATER SYSTEM - FREEZE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

WATER SYSTEM - HARVEST<br />

1ST PART - FIRST 6” - WATER PURGE OUT


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

WATER SYSTEM - HARVEST<br />

2ND PART - UP TO THE END OF HARVEST<br />

OFF


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - REFRIGERANT SYSTEM<br />

LOCATION OF REFRIGERANT COMPONENTS<br />

The components of the refrigerant<br />

system of the <strong>MV</strong> series Models are<br />

composed by:<br />

• COMPRESSOR


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - REFRIGERANT SYSTEM<br />

LOCATION OF REFRIGERANT COMPONENTS<br />

The components of the refrigerant<br />

system of the <strong>MV</strong> series Models are<br />

composed by:<br />

• COMPRESSOR<br />

• CONDENSER


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - REFRIGERANT SYSTEM<br />

LOCATION OF REFRIGERANT COMPONENTS<br />

The components of the refrigerant<br />

system of the <strong>MV</strong> series Models are<br />

composed by:<br />

• COMPRESSOR<br />

• CONDENSER<br />

• EVAPORATOR


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - REFRIGERANT SYSTEM<br />

LOCATION OF REFRIGERANT COMPONENTS<br />

The components of the refrigerant<br />

system of the <strong>MV</strong> series Models are<br />

composed by:<br />

• COMPRESSOR<br />

• CONDENSER<br />

• EVAPORATOR<br />

• TXV VALVE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - REFRIGERANT SYSTEM<br />

LOCATION OF REFRIGERANT COMPONENTS<br />

The components of the refrigerant<br />

system of the <strong>MV</strong> series Models are<br />

composed by:<br />

• COMPRESSOR<br />

• CONDENSER<br />

• EVAPORATOR<br />

• TXV VALVE<br />

• HEAT EXCHANGER


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - REFRIGERANT SYSTEM<br />

LOCATION OF REFRIGERANT COMPONENTS<br />

The components of the refrigerant<br />

system of the <strong>MV</strong> series Models are<br />

composed by:<br />

• COMPRESSOR<br />

• CONDENSER<br />

• EVAPORATOR<br />

• TXV VALVE<br />

• HEAT EXCHANGER<br />

• DRIER


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - REFRIGERANT SYSTEM<br />

LOCATION OF REFRIGERANT COMPONENTS<br />

The components of the refrigerant<br />

system of the <strong>MV</strong> series Models are<br />

composed by:<br />

• COMPRESSOR<br />

• CONDENSER<br />

• EVAPORATOR<br />

• TXV VALVE<br />

• HEAT EXCHANGER<br />

• DRIER<br />

• HOT GAS VALVE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - REFRIGERANT SYSTEM<br />

LOCATION OF REFRIGERANT COMPONENTS<br />

The components of the refrigerant<br />

system of the <strong>MV</strong> series Models are<br />

composed by:<br />

• COMPRESSOR<br />

• CONDENSER<br />

• EVAPORATOR<br />

• TXV VALVE<br />

• HEAT EXCHANGER<br />

• DRIER<br />

• HOT GAS VALVE<br />

• HIGH PRESSURE CTRL


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - WATER SYSTEM<br />

• WATER INLET VALVE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - WATER SYSTEM<br />

• WATER INLET VALVE<br />

• WATER SUMP


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - WATER SYSTEM<br />

• WATER FLOAT VALVE<br />

• WATER SUMP<br />

• WATER PUMP


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - WATER SYSTEM<br />

• WATER FLOAT VALVE<br />

• WATER SUMP<br />

• WATER PUMP<br />

• WATER DISTRIBUTOR<br />

PAN


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - WATER SYSTEM<br />

• WATER INLET VALVE<br />

• WATER SUMP<br />

• WATER PUMP<br />

• WATER DISTRIBUTOR PAN<br />

• WATER DRAIN VALVE


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - WATER SYSTEM<br />

• WATER INLET VALVE<br />

• WATER SUMP<br />

• WATER PUMP<br />

• WATER DISTRIBUTOR PAN<br />

• WATER DRAIN VALVE<br />

• HARVEST ASSIST<br />

SOLENOID


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

FAN<br />

MOTORS<br />

PC BOARD<br />

COMPRESSOR, HOT GAS, WATER<br />

INLET AND DRAIN VALVES<br />

POWER IN<br />

AND SAFETY<br />

PRESSURE<br />

CONTROLS<br />

FUSE<br />

WATER<br />

PUMP<br />

N.O. - JUMP OUT<br />

AUTOMATIC<br />

N.C. - JUMP IN<br />

MANUAL<br />

- +<br />

J2<br />

WATER<br />

SENSITIVITY<br />

ADJUSTMENT<br />

J1<br />

FOR<br />

FACTORY<br />

USE ONLY<br />

SERIAL<br />

CONNECTOR<br />

DISPLAY<br />

CONNECTOR<br />

ICE THICKNESS<br />

SENSOR<br />

WATER LEVEL<br />

SENSOR<br />

MAGNETIC<br />

SWITCH<br />

CONDENSER<br />

SENSOR


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

The PC Board can be<br />

set up for:<br />

Manual reset and<br />

one water filling at<br />

beginning of the<br />

Freezing Cycle<br />

(JUMP IN)<br />

SETTING OF PC BAORD


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

The PC Board can be<br />

set up for:<br />

Automatic reset<br />

and continuous<br />

water filling mode<br />

during the Freezing<br />

Cycle (JUMP OUT)<br />

SETTING OF PC BAORD


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - ELECTRONIC CONTROLS<br />

The components of the<br />

Electronic System of the<br />

<strong>MV</strong> Series Models are<br />

composed by:<br />

• PC BOARD


COMPONENTS - ELECTRONIC CONTROLS<br />

• PC BOARD<br />

• ICE<br />

<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

THICKNESS<br />

SENSOR


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - ELECTRONIC CONTROLS<br />

• PC BOARD<br />

• ICE THICKNESS<br />

SENSOR<br />

• CONDENSER<br />

SENSOR


<strong>MV</strong> <strong>306</strong>-<strong>456</strong><br />

<strong>456</strong>-<strong>606</strong>-<strong>806</strong>-<strong>1006</strong><br />

COMPONENTS - ELECTRONIC CONTROLS<br />

• PC BOARD<br />

• ICE THICKNESS<br />

SENSOR<br />

• CONDENSER<br />

SENSOR<br />

• MAGNETIC<br />

SWITCH


END FIRST<br />

HALF