Modicon M340<br />

Programmable Automation Controller<br />

Analog I/O modules<br />

Type of module<br />

Analog input module<br />

2<br />

Input type<br />

Isolated high-level<br />

inputs<br />

Isolated high-level<br />

inputs<br />

Non isolated<br />

high-level inputs<br />

Isolated inputs, low-level voltage, resistors,<br />

temperature probes, thermocouples<br />

Number of channels 4 8 8 4 8<br />

Nature of inputs<br />

± 10 V, ± 5 V, 0…5 V, 0…10 V, 1…5 V<br />

0…20 mA, 4…20 mA , ± 20 mA<br />

±40 mV, ±80 mV, ±160 mV, ±320 mV,<br />

±640 mV, ±1.28 V<br />

Resolution 0.35 mV/0.92 µA 15 mV + sign<br />

References BMXAMI0410 BMXAMI0810 (1) BMXAMI0800 (1) BMXART0414 BMXART0814<br />

Type of module<br />

Analog output module<br />

Output type Isolated high-level outputs Non isolated high-level outputs<br />

Number of channels 2 4 8<br />

Range Voltage ± 10 V –<br />

Current 0…20 mA and 4…20 mA –<br />

Resolution<br />

15 bits + sign<br />

References BMXAMO0210 BMXAMO0410 (1) BMXAMO0802 (1)<br />

Type of module<br />

Mixed analog I/O module<br />

Channel type Non-isolated high-level inputs Non-isolated high-level outputs<br />

Number of channels 4 2<br />

Ranges ±10 V, 0…5 V, 0…10 V, 1…5 V, 0…20 mA, 4…20 mA ±10 V, 0…20 mA, 4…20 mA<br />

Maximum conversion value Voltage ± 11.25 V ± 11.25 V<br />

Current 0…30 0…24 mA<br />

Resolution 14 bits, 12 bits, 13 bits, 12 bits 12 bits, 11 bits<br />

Reference<br />

BMXAMM0600<br />

Counter and motion control modules<br />

Type of module Counter module Motion Control<br />

32 bits 16 bits 32 bits Module<br />

Modularity 2 channels 8 channels 4 channels 4 channels<br />

No. of sensor inputs 6 per channel 2 per channel 3 per channel 4 auxiliary inputs<br />

No. of actuator outputs 2 per channel 2 auxiliary outputs<br />

Module cycle time 1 ms 5 ms –<br />

Applications<br />

Upcounting, downcounting,<br />

measurement, frequency meter,<br />

frequency generator, axis following<br />

Upcounting, downcounting,<br />

measurement<br />

Frequency generator, Move,<br />

set position<br />

References BMXEHC0200 BMXEHC0800 BMXMSP0200<br />

2/36<br />