26.06.2014 Views

3000DB0902 ZSI Application Note - Schneider Electric

3000DB0902 ZSI Application Note - Schneider Electric

3000DB0902 ZSI Application Note - Schneider Electric

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Data Bulletin<br />

<strong>3000DB0902</strong><br />

05/2009<br />

LaVergne, TN, USA<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

Class Number 3000<br />

What is <strong>ZSI</strong>?<br />

Zone Selective Interlocking (<strong>ZSI</strong>) is a communication-based protection<br />

scheme built into the firmware of the SEPAM MV protective relays. The<br />

basic idea involves a downstream breaker sending a blocking signal to an<br />

upstream breaker. The blocking signal blocks a high(er) speed tripping<br />

element.<br />

All devices within the <strong>ZSI</strong> system have backup elements which are<br />

independent of the high speed scheme. The normal result of a <strong>ZSI</strong> system<br />

for through faults is the high speed elements are blocked and standard time<br />

overcurrent elements are ready to provide backup protection. If the fault is<br />

internal to the <strong>ZSI</strong> zone, a high speed (typically 100-200ms) trip will occur.<br />

Refer to Figure 1 and Figure 2 below.<br />

Figure 1: Fault Downstream of F1 Figure 2: Fault Upstream of F1<br />

Communication is done via inputs and outputs on the SEPAM relay at<br />

control power voltage (typically 125Vdc or 110Vac), and not by low millivolt<br />

signals susceptible to noise. The inputs and outputs represent almost no<br />

burden, blocking signal distances of ½ mile show very little voltage drop<br />

(with 125Vdc control power).<br />

<strong>ZSI</strong> in its simplest form (Figures 1 and 2) provides the basic idea of the<br />

scheme, however this idea can be expanded to use multiple feeders (Figure<br />

3), multiple mains and a tie breaker (Figures 5 and 5a), and a complex ring<br />

bus arrangement (Figure 6).<br />

The purpose of this paper is to provide a thorough understanding of the <strong>ZSI</strong><br />

scheme so an engineer can design, wire and program the SEPAM relays<br />

(with SFT2841 software).<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

Why use <strong>ZSI</strong>?<br />

The primary use of <strong>ZSI</strong> is the ability to trip faster than the normal overcurrent<br />

(ANSI 50/51 elements) coordinating interval. The result of tripping faster is<br />

significant reduction of arc flash energy. This reduction is at the expense of<br />

a couple of control wires per circuit; however it is NOT at the expense of<br />

coordination.<br />

Below is a table that indicates the AF energy for 5kA, 10kA, 20kA, 30kA and<br />

50kA bolted three phase faults at voltage levels of 4160V and 13.8kV.<br />

Table 1:<br />

Arc Flash Results for a 100ms <strong>ZSI</strong> system<br />

Bus Name<br />

kH represents<br />

bolted 3PH<br />

fault current<br />

Protective<br />

Device<br />

Name<br />

Bus<br />

kV<br />

Bus<br />

Bolted<br />

Fault<br />

(kA)<br />

Prot<br />

Dev<br />

Bolted<br />

Fault<br />

Prot Dev<br />

Arcing<br />

Fault<br />

(kA)<br />

Trip/<br />

Delay<br />

Time<br />

(sec.)<br />

Breaker<br />

Opening<br />

Time<br />

(sec.)<br />

Ground Equip<br />

Type<br />

Arc Flash Working Incident<br />

Gap<br />

BoundaryDistance<br />

Energy<br />

(mm)<br />

(in) (in) (cal/cm2)<br />

Required<br />

Protective<br />

FR<br />

Clothing<br />

4160V_5kA <strong>ZSI</strong>_0.1_5kA 4.16 5 5 4.91 0.1 0.083 Yes SWG 104 29 36 0.96 Category 0<br />

4160V_10kA <strong>ZSI</strong>_0.1_10kA 4.16 10 10 9.71 0.1 0.083 Yes SWG 104 62 36 2 Category 1<br />

4160V_20kA <strong>ZSI</strong>_0.1_20kA 4.16 20 20 19.18 0.1 0.083 Yes SWG 104 131 36 4.2 Category 2<br />

4160V_30kA <strong>ZSI</strong>_0.1_30kA 4.16 30 30 28.58 0.1 0.083 Yes SWG 104 204 36 6.5 Category 2<br />

4160V_50kA <strong>ZSI</strong>_0.1_50kA 4.16 50 50 47.21 0.1 0.083 Yes SWG 104 357 36 11 Category 3<br />

13800V_5kA <strong>ZSI</strong> 0.1_5kA 13.8 5 5 4.91 0.1 0.083 Yes SWG 153 33 36 1.1 Category 0<br />

13800V_10kA <strong>ZSI</strong> 0.1_10kA 13.8 10 10 9.71 0.1 0.083 Yes SWG 153 70 36 2.3 Category 1<br />

13800V_20kA <strong>ZSI</strong> 0.1_20kA 13.8 20 20 19.18 0.1 0.083 Yes SWG 153 149 36 4.8 Category 2<br />

13800V_30kA <strong>ZSI</strong> 0.1_30kA 13.8 30 30 28.58 0.1 0.083 Yes SWG 153 232 36 7.3 Category 2<br />

13800V_50kA <strong>ZSI</strong> 0.1_50kA 13.8 49.99 49.99 47.21 0.1 0.083 Yes SWG 153 405 36 13 Category 3<br />

Table 2:<br />

Arc Flash Results for a 200ms <strong>ZSI</strong> system<br />

Bus Name<br />

Protective<br />

Device<br />

Name<br />

Bus<br />

kV<br />

Bus<br />

Bolted<br />

Fault<br />

(kA)<br />

Prot Dev<br />

Bolted<br />

Fault<br />

(kA)<br />

Prot Dev<br />

Arcing<br />

Fault<br />

(kA)<br />

Trip/<br />

Delay<br />

Time<br />

(sec.)<br />

Breaker<br />

Opening<br />

Time<br />

(sec.)<br />

Ground Equip<br />

Type<br />

Arc Flash Working Incident<br />

Gap<br />

Boundary Distance Energy<br />

(mm)<br />

(in) (in) (cal/cm2)<br />

Required<br />

Protective<br />

FR Clothing<br />

Category<br />

A_4160V_5kA <strong>ZSI</strong>_0.2_5kA 4.16 5 5 4.91 0.2 0.083 Yes SWG 104 45 36 1.5 Category 1<br />

B_4160V_10kA <strong>ZSI</strong>_0.2_10kA 4.16 10 10 9.71 0.2 0.083 Yes SWG 104 96 36 3.1 Category 1<br />

C_4160V_20kA <strong>ZSI</strong>_0.2_20kA 4.16 20 20 19.18 0.2 0.083 Yes SWG 104 205 36 6.5 Category 2<br />

D_4160V_30kA <strong>ZSI</strong>_0.2_30kA 4.16 30 30 28.58 0.2 0.083 Yes SWG 104 320 36 10 Category 3<br />

E_4160V_50kA <strong>ZSI</strong>_0.2_50kA 4.16 50 50 47.21 0.2 0.083 Yes SWG 104 558 36 17 Category 3<br />

F_13800V_5kA <strong>ZSI</strong> 0.2 5kA 13.80 5 5 4.91 0.2 0.083 Yes SWG 153 51 36 1.7 Category 1<br />

G_13800V_10kA <strong>ZSI</strong> 0.2 10kA 13.80 10 10 9.71 0.2 0.083 Yes SWG 153 109 36 3.5 Category 1<br />

H_13800V_20kA <strong>ZSI</strong> 0.2 20kA 13.80 20 20 19.18 0.2 0.083 Yes SWG 153 233 36 7.4 Category 2<br />

I_13800V_30kA <strong>ZSI</strong> 0.2 30kA 13.80 30 30 28.58 0.2 0.083 Yes SWG 153 363 36 11 Category 3<br />

J_13800V_50kA <strong>ZSI</strong> 0.2 50kA 13.80 49.99 49.99 47.21 0.2 0.083 Yes SWG 153 634 36 19 Category 3<br />

Most 4160V systems have bolted three phase fault currents less than 20-<br />

30kA. From the table the incident energies are 4.2 and 6.5 cal/cm 2 , both of<br />

these results in Cat 2 PPE.<br />

A 10MVA base rated, 6% impedance transformer has an infinite bus let<br />

through of 23,131A at 4160V. A 25MVA base rated, 6% impedance<br />

transformer has an infinite bus let through of 17,432A at 13.8kV. Most<br />

industrial applications have 5kV buses that are fed from transformers<br />

smaller than 10MVA and 15kV buses smaller than 25MVA. The conclusion<br />

is that for most industrial applications, the <strong>ZSI</strong> will limit the AF energies to<br />

CAT 2 or below.<br />

If AF reduction is the main desire in a normal system design, the<br />

conventional bus differential relay (87B) will typically have an AF category of<br />

2<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

zero. The differential requires dedicated ct’s all sized the same. In this<br />

respect the 87B and the <strong>ZSI</strong> do not “compete”. However, if the fault currents<br />

are limited to values that are below a desired AF category, or if there is an<br />

existing lineup of switchgear that requires AF reduction, the <strong>ZSI</strong> becomes a<br />

very cost-effective solution.<br />

The <strong>ZSI</strong> scheme can be cascaded, without the need for coordination. One<br />

“zone” may include the main bus of a switchgear lineup, another zone may<br />

include a feeder breaker that has a conductor run of 2000 feet. Each of<br />

these zones can have <strong>ZSI</strong> time delays of 100-200ms. If a fault does occur in<br />

the 2000 foot run of cable, the feeder that feeds the fault would block the<br />

main <strong>ZSI</strong> from tripping high speed, the feeder would not receive a blocking<br />

signal from the breaker that the conductor terminates into, and therefore<br />

would trip high speed.<br />

Where is <strong>ZSI</strong> used?<br />

Square D Company began developing low voltage (LV -480 volt) <strong>ZSI</strong><br />

technology in 1986, and began using <strong>ZSI</strong> extensively in 480 volt substations<br />

in 1988. At that time the term “Arc Flash” was virtually unknown, and the<br />

electrical phenomena that dominated the trade magazines was the effects<br />

of harmonic distortion on the power system.<br />

The application of the 480 volt <strong>ZSI</strong> is almost identical to the MV design.<br />

Most people believe the MV design is easier to troubleshoot. This stems<br />

from the inherent information available in modern day digital relays versus<br />

the low-voltage trip units where virtually none exist.<br />

The most recent application of <strong>ZSI</strong> is between LV trip units and MV relays.<br />

Refer to Figure 7. A complete technical paper written by Van Wagner is also<br />

included in the Appendix.<br />

<strong>ZSI</strong> is used in the following MV applications:<br />

• Only within an MV lineup of switchgear (provides high-speed trip for bus<br />

fault). Refer to Figures 3, 5 and 5a.<br />

• Between separated radial MV lineups of switchgear (provides highspeed<br />

trip for conductor fault). This scheme trips one breaker and<br />

removes service to all loads downstream of a tripped breaker. Refer to<br />

Figure 4.<br />

• Between separated looped MV lineups of switchgear (provides highspeed<br />

trip for conductor fault). This scheme trips two breakers to clear<br />

fault, but maintains service to other loads. Refer to Figure 6.<br />

• LV trip units to “virtual” 480V device (MV Relay) (provides AF<br />

improvement by tripping MV feeder breaker). Refer to Figure 7.<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 3


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

Figure 3:<br />

MV application of <strong>ZSI</strong> within the lineup<br />

Figure 4:<br />

Radial <strong>ZSI</strong> <strong>Application</strong> for high speed line protection<br />

52<br />

52<br />

4<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

Figure 5:<br />

MV application of <strong>ZSI</strong> M-T-M<br />

Figure 5a:<br />

Alternate MV application of <strong>ZSI</strong> M-T-M (Non-relayed Tie)<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 5


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

Figure 6:<br />

Closed Loop / Ring Bus <strong>Application</strong><br />

6<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

Figure 7:<br />

Low Voltage MicroLogic trip units supply blocking signals to<br />

“virtual” main with SEPAM relay<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 7


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

MV <strong>Application</strong>s<br />

<strong>Application</strong> 1 – Simple Main / Feeder <strong>ZSI</strong><br />

Figure shows the control diagram for the main breaker shown in Figure 3, a<br />

single main with two feeders. The main breaker receives two contacts, O3<br />

from the SEPAM relay connected to Fdr 1 and O3 from the SEPAM relay<br />

connected to Fdr 2. If either one of these contacts close, then I13 (the input<br />

on the SEPAM relay connected to the main breaker) would activate blocking<br />

of the high speed <strong>ZSI</strong> scheme and the main would not trip the <strong>ZSI</strong> element.<br />

Figure 8:<br />

Main Bkr Control Diagram for a single main and two feeder<br />

system in Figure 3..<br />

Figure 9 shows the SFT2841 Program Logic settings for the Main and<br />

Figure 9a shows the SFT2841 protection settings for the feeders.<br />

8<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

Figure 9:<br />

SFT2841 Program Logic Settings for Main<br />

I13 accepts the blocking contacts from feeders<br />

I11 accepts the 52b contact<br />

I12 accepts the 52a contact<br />

Figure 9a:<br />

SFT2841 Program Logic Settings for Feeders (also see Figure<br />

11a) which only require an output assignment, in this case O3.<br />

Figure 10 shows the SFT2841 protection settings for the Main and Figure<br />

10a shows the SFT2841 protection settings for the feeders.<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 9


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

Figure 10: SFT2841 protection settings for the Main (only Elements 1<br />

and 3 are need for both <strong>ZSI</strong> and the backup Time-based 51<br />

setting).<br />

Figure 10a: SFT2841 protection settings for the Feeders<br />

Keep in mind that the last relay in the <strong>ZSI</strong> scheme blocks ONLY. The<br />

tripping for this position in the <strong>ZSI</strong> scheme is performed by the standard<br />

50/51 elements.<br />

Figure 11: SFT2841 Control Matrix for the Main<br />

10<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

Figure 11a: SFT2841 Control Matrix for the Feeders<br />

Recommended outputs for <strong>ZSI</strong>:<br />

Series 20/40 – O3 and O12 (if needed)<br />

Series 80 – O102 (Block Direction 1), O103 (Block Direction 2)<br />

These recommended output assignments are made to avoid a conflict with<br />

other frequently used assignments. Worth mentioning is the “remote close<br />

via communication”, this function is pre-programmed in the Series 20/40 as<br />

O11, in the Series 80 it is O3. This is believed to be an ever increasing<br />

application because it allows circuit breakers to be closed without an<br />

operator standing in front of the switchgear. Presently there is a demand for<br />

the Square D Field Services designed remote open/close and racking<br />

device.<br />

Recommended inputs for <strong>ZSI</strong>:<br />

Series 20/40 – I13 (Direction 1 – Series 20 only has 1 direction)<br />

Series 40 – I21 (Direction 2)<br />

Series 80 – I104 (Direction 1), I105 (Direction 2)<br />

NOTE: A further discussion on the meaning of “direction” is included in the<br />

application of the closed ring.<br />

General Procedure:<br />

1. Wire I/O<br />

2. Configure Program Logic page<br />

3. Configure Control Matrix<br />

4. Configure Protection Tab which includes<br />

a. <strong>ZSI</strong> settings<br />

b. Phase Over current settings<br />

c. Ground Over Current settings<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 11


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

The <strong>ZSI</strong> scheme requires specific settings for the main and feeders. It is<br />

common for application engineers to set the <strong>ZSI</strong> (phase) pickup setting per<br />

Table 3 below:<br />

Table 3:<br />

<strong>ZSI</strong> “Common” Pickup Settings for Blocking to Occur<br />

Switchgear Main Bus Min. PU * Max PU<br />

1200A 2.4-3.6kA ½ maximum three phase fault current.<br />

2000A 4-6kA ½ maximum three phase fault current.<br />

3000A 6-9kA ½ maximum three phase fault current.<br />

*Min. PU assumes that the short circuit contribution from motors is less than<br />

the pickup value. If there is a system that has a significant motor<br />

contribution in the <strong>ZSI</strong> zone, perform the following steps:<br />

Increase the time delay of the scheme to 200ms.<br />

Use directional 67 element (pointing in the forward direction) to block<br />

only if the fault is downstream of the feeder. The motor contribution<br />

would be in the reverse direction.<br />

Within a given scheme, all relays typically have the same pickup. The<br />

ground fault <strong>ZSI</strong> pickups are commonly set to 50-87% of the phase settings<br />

for a solidly grounded system. The common time delays are 100ms. As<br />

mentioned above, there may be instances where motor contribution at one<br />

level of the <strong>ZSI</strong> may cause the time delay to be 200ms and the time delays<br />

near the utility to be 100ms (the SEPAM instruction book shows this<br />

example).<br />

Protection for most industrial feeder breakers typically allow for a ANSI 50<br />

function (instantaneous). In the example above, the <strong>ZSI</strong> blocking is set up to<br />

2.4kA and the feeder breakers also trip at 2.4kA. The feeder 50 setting is<br />

typically set to1.7 x maximum inrush. So if there is a fault downstream of the<br />

feeder of 3000A, the feeder would send a blocking signal to the main and<br />

simultaneously trip the feeder. Once the trip signal is sent to the feeder, the<br />

blocking signal is released 200 ms later. If the feeder breaker did not clear<br />

the fault (i.e. failed to operate), the main would immediately trip to clear the<br />

fault. Therefore the <strong>ZSI</strong> scheme has a built-in breaker failure protection.<br />

If a feeder feeds multiple transformers and an ANSI 50 element is not used,<br />

the downstream 3000A fault would be allowed to flow until the feeder 51<br />

element cleared (if a downstream transformer primary fuse did not clear the<br />

fault). If this were the case, the feeder would send and maintain the blocking<br />

signal and the main would not trip on the high speed element. The feeder 51<br />

element would eventually trip (based on its setting).<br />

<strong>Application</strong> 2 – Main-Tie-Main The normal Main-Tie-Main (M-T-M) is very common to <strong>Application</strong> 1<br />

covered in detail above. In the M-T-M, the feeders have a second output<br />

contact to block the TIE (O12 refer to Figure 12). All settings for the feeder<br />

are the same. The TIE and Main settings in the M-T-M are just like the Main<br />

in <strong>Application</strong> 1. TIE is slightly different in that it blocks both Mains (O12<br />

blocks M1 and O3 blocks M2); the <strong>ZSI</strong> pickup and time delay settings are<br />

the same as the Main.<br />

12<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

Figure 12:<br />

M-T-M <strong>ZSI</strong> with I/O labeled for SEPAM Series 20/40 with I/O<br />

assignments.<br />

In Figure 12 assume the TIE is closed and M2 is Open.<br />

Table 4:<br />

SC1, SC2 & SC3 Block and Trip Summary<br />

Short Circuit Event CB Blocked / Blocked By / Output Contact Trip<br />

SC1 TIE / F4 / O12 and M1 / TIE / O12 F4<br />

SC2 M1 / TIE / O12 TIE<br />

SC3 NONE M1<br />

<strong>Note</strong> that in “SC1 and SC2” the TIE breaker sends a blocking signal to M2<br />

but in these cases this breaker is already open. If the N.O. TIE is closed<br />

then either M1 or M2 must be open. With this scheme, there is no need to<br />

write Boolean logic. Blocking both mains works well for this situation. If the<br />

TIE is NC, then this configuration would be considered a “closed loop” which<br />

is covered in the next application example.<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 13


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

<strong>Application</strong> 3 – Closed Loop System Refer to Figure 6 and Figure 13.<br />

Figure 13: Closed Loop <strong>ZSI</strong> with I/O assignments<br />

The closed loop system is a system that has multiple sources that are<br />

normally tied together. This could be the case with a facility that has two<br />

separate utility feeds (most common), or a system that has one utility feed<br />

and one or more generators (common in paper mills).<br />

The benefits of this scheme are commonly used in the “critical power” area.<br />

This scheme requires a more thorough knowledge of all the power system<br />

disciplines. Special care is required when multiple sources are tied together<br />

to make certain the switchgear interrupting ratings are adequate and that<br />

reverse current relays (ANSI 67 and 67N) elements are properly applied<br />

and tested. This scheme also requires a higher level of safety training for<br />

operators and technicians. When a circuit breaker is opened in the loop, it is<br />

more likely than not that the line and load side of the breaker is still hot.<br />

The basis of the closed loop <strong>ZSI</strong> is that within the portion of the system that<br />

is closed, each relay has two 67 elements; one looking in the forward<br />

direction and one looking in the reverse (Figure 13). The 67 Element 1 (67-<br />

1) is typically pointing in the reverse direction. The convention for choosing<br />

the direction for the relays in the system is somewhat arbitrary. Following a<br />

14<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

consistent convention is recommended. Below is convention that has<br />

worked well:<br />

1. Choose all 67-1 directional elements in the reverse direction of normal<br />

current flow (into non-polarity, out of the polarity marks on the CT). 67-2<br />

is always in the opposite direction as 67-1.<br />

2. Eventually there are feeder breakers that are not in the “closed loop” (i.e.<br />

they cannot produce a constant source of fault current) these feeders do<br />

not require 67 elements; the non-directional 50 settings work fine<br />

(unless the motor contribution is in excess of the desired pickup value).<br />

3. The I/O are associated with a specific direction.<br />

a. Series 80 Inputs:I 104-Rev; I105- Fwd<br />

b. Series 80 Outputs: O102, O104*, O106* - Rev<br />

O103, O105*, O107* - Fwd<br />

c. Series 40 Inputs: I13 – Rev; I21 - Fwd<br />

d. Series 40 Outputs:O3, O12* - Rev<br />

O13, O14 – Fwd<br />

* = If needed.<br />

Direction 1 corresponds with “Rev”. Direction 2 corresponds with “Fwd”<br />

4. Figure 13 output contacts also have arrowheads indicating which 67<br />

element they work in conjunction with. Since blocking is always<br />

“backwards”, the arrowhead of an output contact never points toward an<br />

input, but instead it will always point away from an input. Study Figure 13<br />

and follow the blocking contacts for a 67-1 element and a 67-2 element.<br />

In the examples for Figures 14-15 it is assumed that the Mains and Ties<br />

have Series 80 SEPAM relays and the feeders have Series 40.<br />

Short Circuit Events (SC1 and SC2 in the closed loop system)<br />

SC1 – refer to Figure 14<br />

F2a does not have dual 67 elements since it has been determined that the<br />

load downstream of F2a does not have either a generator, utility or large<br />

motor contribution. The non-directional element at F2a would block (via O3<br />

and O12) TIE-a and M2a elements that can provide fault current to F2a. F2a<br />

would trip on it’s time based 50/51 setting.<br />

Table 5: SC1 Block and Trip Summary<br />

Short Circuit Event CB Blocked / Blocked By / Output Contact Trip<br />

SC1 TIE-a and M2a / F2a / O12 and O3 F2a<br />

F2 / M2a / O103<br />

M1a / TIE-a / O103<br />

F1 / M1a / O103<br />

TIE and M2 / F2 / O14 and O13<br />

TIE and M1 / F1 / O14 and O13<br />

All the breakers in this example are blocked from high speed tripping except<br />

F1a (which does not see the fault) and F2a which trips.<br />

A 67 element will not trip if either of the following is true:<br />

It is blocked by a downstream relay that also sees the fault in the proper<br />

direction.<br />

The fault is not in the direction of the element.<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 15


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

Figure 14:<br />

Fault Example SC1<br />

SC-2 Refer to Figure 15.<br />

When a fault is detected by a directional element, the <strong>ZSI</strong> blocks backwards<br />

to the source breakers that can provide fault current in that direction. For<br />

fault SC2 the 67-2 element at F1 senses current in “its” direction and closes<br />

the two output contacts that match the forward direction, in this case O13<br />

and O14. These two contacts block the forward flowing element in M1 from<br />

tripping (67-2) and the TIE element 67-1. The 67-1 in M1 or 67-2 in the TIE<br />

does not see fault current in “their” direction. The TIE 67-1 element also<br />

blocks backwards which includes M2 67-2 and F2 67-1.<br />

16<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

Since the fault current coming in from M2 can split, some going through the<br />

TIE and some going through F2, M2a, TIE-a, M1a to fault, this loop must<br />

also be blocked. See the table below for complete blocking sequence.<br />

Table 6: SC2 Block and Trip Summary<br />

Short Circuit Event<br />

SC2<br />

CB Blocked / Blocked By / Output Contact Trip (Element)<br />

M1 and TIE / F1/ O13 and O14<br />

F1 does not receive blocking from M1a and Trips F1 (67-2)<br />

M2 and F2 / TIE / O102 and O104<br />

TIE and M2 / F2 / O14 and O13<br />

F2 / M2a / O103<br />

M1a does not receive blocking from F1 and Trips M1a (67-1)<br />

M2a / TIE-a / O102<br />

So the faulted line segment between breakers F1 and M1a is cleared<br />

quickly by the <strong>ZSI</strong> scheme and the rest of the load continues to operate.<br />

<strong>Note</strong> that some breakers are blocked more than once; the TIE is blocked by<br />

F1 and F2. The F2 block is in a direction that the TIE 67-2 element which is<br />

not picked up, so nothing occurs. Faults downstream of F2 could cause<br />

current to flow across the TIE in the 67-2 direction so this blocking is<br />

necessary.<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 17


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

Figure 15:<br />

Fault Scenario SC2<br />

18<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

SEPAM SFT2841 Settings for Closed Loop <strong>ZSI</strong> Figure 16: Closed Loop <strong>ZSI</strong> Main and Tie 51 Settings<br />

In the closed loop system, the 67 elements (see Figure 17) perform the<br />

blocking and tripping functions, therefore only the backup time based 51<br />

settings are needed.<br />

Figure 17: Closed Loop <strong>ZSI</strong> Main and Tie 67 setting example.<br />

Figure 18:<br />

Closed Loop <strong>ZSI</strong> Control Matrix – Logic/Outputs<br />

Figure 19:<br />

Closed Loop <strong>ZSI</strong> Control Matrix – Protection/Outputs<br />

A subtle but important point is that the blocking assignments are made in<br />

the Logic/Output section of the control matrix, not the Protection/Outputs<br />

page (refer to Figures 18 and 19). The gray outputs are the outputs<br />

controlled by the “Circuit Breaker Control” (ON) setting.<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 19


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

05/2009<br />

Figure 20: Series 40 Feeder in the Closed Loop <strong>ZSI</strong> - 51<br />

The feeders in the closed loop have the same setting philosophy, the 67<br />

elements block and trip and the 51 element is for backup (see Figures 20<br />

and 21).<br />

Figure 21: Series 40 Feeder in the Closed Loop <strong>ZSI</strong> – 67<br />

20<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved


<strong>3000DB0902</strong><br />

05/2009<br />

Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong><br />

Control Diagram Figure 22: Control Diagram with “external” block sending and receiving<br />

A<br />

PTD<br />

1<br />

M7<br />

M8<br />

I13<br />

<strong>ZSI</strong> BLOCKING<br />

RECEPTION 1<br />

DL5C<br />

MES114<br />

S4D<br />

RTO<br />

13<br />

RTO<br />

14<br />

M1<br />

M2<br />

I11<br />

DL5C<br />

MES114<br />

S4D<br />

M4<br />

M5<br />

I12<br />

DL5C<br />

MES114<br />

S4D<br />

A1<br />

L(+)<br />

DL5C<br />

S40<br />

POWER<br />

SUPPLY<br />

RTO<br />

1<br />

RTO<br />

3<br />

125VDC<br />

SOURCE<br />

RTD<br />

5<br />

BLOCKING SIGNAL<br />

FROM T3-N-01 5069<br />

PO#24383883-007<br />

MAIN BREAKER<br />

RTD<br />

6<br />

53<br />

12<br />

13<br />

54<br />

RTN<br />

15<br />

SDL<br />

52<br />

/b<br />

RTN<br />

16<br />

56<br />

21<br />

22<br />

60<br />

RTN<br />

21<br />

SDL<br />

52/d<br />

RTN<br />

22<br />

N(-)<br />

A2<br />

0<br />

GRD<br />

G 10<br />

A10<br />

A11<br />

DL5C<br />

S4D<br />

03<br />

RTO<br />

2<br />

BLOCKING SIGNAL<br />

BREAKER 52-M1<br />

L5<br />

L6<br />

DL5C<br />

MES114<br />

012<br />

RTO<br />

4<br />

BLOCKING SIGNAL<br />

BREAKER 52-T<br />

B<br />

PTD<br />

2<br />

What is unique to this scheme in comparison to the M-T-M scheme is that<br />

care must be taken so that the two different lineups of switchgear do not tie<br />

DC power (typically 125Vdc) sources together.<br />

The convention used by the Square D Company switchgear plant in<br />

Smyrna, TN is to power the dry output contacts with the DC voltage from the<br />

“input” location. With this convention, the dry contacts are whetted at the<br />

location of the inputs. Refer to Figure 22.<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved 21


Sepam <strong>ZSI</strong> <strong>Application</strong> <strong>Note</strong> <strong>3000DB0902</strong><br />

Data Bulletin 05/2009<br />

<strong>Schneider</strong> <strong>Electric</strong> USA<br />

Street Address<br />

City, State Zip Country<br />

1-888-SquareD (1-888-778-2733)<br />

www.schneider-electric.us<br />

Square D ® is a trademark or registered trademark of <strong>Schneider</strong> <strong>Electric</strong>. Other<br />

trademarks used herein are the property of their respective owners.<br />

<strong>Electric</strong>al equipment should be installed, operated, serviced, and maintained only by<br />

qualified personnel. No responsibility is assumed by <strong>Schneider</strong> <strong>Electric</strong> for any<br />

consequences arising out of the use of this material.<br />

22<br />

© 2009 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!