8 Multicare Function<br />
Two inverter drives can be operated simultaneously in “tandem mode” by utilizing the multicare function.<br />
The two drives are connected together using their analog outputs and analog inputs. The analog output<br />
of one drive is connected to the analog input of the other drive, and vice versa. Both drives alter the<br />
voltage value of their own analog output signal according to run conditions whenever the multicare mode<br />
is selected. The table below shows the input (receive) and output (send) values during start, acceleration,<br />
stopping and in fault situation. The multicare function is selected with an input parameter (P2.1.5). In<br />
case of multicare fault, a dedicated fault code (F70) is issued. If the operation of one drive is interrupted,<br />
or the drive faults out (for example upper limit fault), the other drive will stop and show multicare fault<br />
(F70). Programmable pushbuttons are used for multicare testing. The multicare function is mainly<br />
designed for EP mode (speed correction possible) but it can also be used in MS (multistep) mode for<br />
run/stop supervision without speed correction.<br />
Ain1 value Input function<br />
(receive)<br />
Aout value Output function<br />
(send)<br />
0…0.2 V Single drive selected. Multicare function not used. 0 V Direction signals S1 and S2 not active in multicare mode.<br />
0.3…0.7 V Brake open acknowledged, acceleration not<br />
0.5 V Brake open, acceleration not allowed.<br />
allowed.<br />
0.8…1.0 V Acceleration allowed. 1.0 V Acceleration allowed.<br />
1…9 V Speed correction range. 1…9 V Speed correction range.<br />
9 V Acceleration acknowledged. 9 V Accelerating.<br />
>9.5 V Fault acknowledged. Immediate brake stop. F70<br />
fault code issued.<br />
10 V Fault. Immediate brake stop.<br />
The multicare function controls and monitors the following situations in multicare mode:<br />
- Both drives start nearly simultaneously (the other drive has 0.5 seconds to respond) and begin to accelerate at<br />
the same time, once both brakes are opened.<br />
- Both drives end up running at the same “reference speed” after acceleration or deceleration (EP hold situation)<br />
– speed correction is not possible at minimum speed or full speed. The correction takes place whenever the<br />
two reference speed values deviate more than 1 %, or about 1 Hz.<br />
- One drive faulting out stops the other and the other drive will issue a multicare fault (F70).<br />
- When only one hoist is selected for operation, the analog signal remains at zero volts and this disables the<br />
multicare mode – in case of one hoist drive being faulty (active fault is not cleared when a starting command is<br />
issued), the analog signal would remain at 10 volts (fault condition) and both hoists would be inoperational. The<br />
solution for allowing the operation of one hoist in single mode, is to open up the analog connection between the<br />
two drives with the help of a small relay (see picture below) – this relay must be capable of connecting DC<br />
current.<br />
8.1 Connections<br />
The analog output of one drive is connected to the analog input of the other drive, and vice versa (see<br />
below). A shielded cable is used to establish the analog signal connection between two drives. Both ends<br />
of the cable shield must be grounded using 360-degree grounding whenever possible.<br />
A<br />
Aout<br />
Ain1+<br />
0V<br />
Ain-<br />
X1:26<br />
X1:23<br />
X1:27<br />
X1:25<br />
X1:23<br />
X1:26<br />
X1:25<br />
X1:27<br />
B<br />
Ain1+<br />
Aout<br />
Ain-<br />
0V<br />
46/79<br />