Freq 0 P2.3.4 Constant current mode frequency limit in percentage of nominal<br />

frequency. Between 0 Hz and Freq 0 current control keeps motor<br />

current in value of P2.3.12 Zero Speed Current.<br />

Freq 1 P2.3.5 Flux current mode frequency limit in percentage of nominal<br />

frequency. Between frequencies Freq 1 and Freq 2 drive is<br />

controlled with special flux current control method.<br />

Freq 2 S1 P2.3.6 Mixed current/voltage mode frequency limit in percentage of nominal<br />

frequency in direction S1. Must not be changed.<br />

Freq 3 S1 P2.3.7 U/f-control mode frequency limit in percentage of nominal frequency<br />

in direction S1. Must not be changed.<br />

Zero Flux Curr P2.3.8 Relative value of flux current of motor. Typical value of this current<br />

control method is 80 %. Parameter is not related to motor real<br />

physical values. Must not be changed.<br />

Stray Flux Curr P2.3.9 Relative value of stray flux current of motor. Typical value of this<br />

current control method is 40 %. Parameter is not related to motor<br />

real physical values. Must not be changed.<br />

Freq 2 S2 P2.3.10 Mixed current/voltage mode frequency limit in percentage of nominal<br />

frequency in direction S2. Must not be changed.<br />

Freq 3 S2 P2.3.11 U/f-control mode frequency limit in percentage of nominal frequency<br />

in direction S2. Must not be changed.<br />

Zero Speed Curr P2.3.12 Relative value of motor current used in small frequencies % of motor<br />

nominal current. Must not be changed.<br />

Min Current Ref P2.3.13 Minimum value of motor current used in current control area % of<br />

motor nominal current. Must not be changed.<br />

Accel Comp TC P2.3.14 Acceleration compensation time constant, which describes rotating<br />

masses of drive system. Physical description of this parameter is a<br />

time, which is needed to accelerate rotating masses from zero to<br />

nominal frequency with motor nominal torque. Must not be changed.<br />

Ref Angle S1 P2.3.15 Voltage / current angle difference S1. 1536 equals 90 angle. Used in<br />

direction changes. Must not be changed.<br />

Ref Angle S2 P2.3.16 Voltage / current angle difference S2. 1536 equals 90 angle. Used in<br />

direction changes. Must not be changed.<br />

Flux Curr Damp P2.3.17 Flux Current Ctrl stabilator time constant in milliseconds. Must not be<br />

changed.<br />

0 – 100 %<br />

0 – 100 %<br />

0 – 100 %<br />

0 – 100 %<br />

0 – 100 %<br />

0 – 100 %<br />

0 – 100 %<br />

0 – 100 %<br />

0 – 250 %<br />

0 – 100 %<br />

0 – 300 s<br />

0 – 3000<br />

0 – 3000<br />

0 – 400 ms<br />

Stop DC-Freq P2.3.18 Defines the frequency at witch DC-braking starts. 0 – 250 Hz<br />

Start Freq S1 P2.3.19 Defines the output frequency during brake opening delay to direction<br />

S1.<br />

Start Freq S2 P2.3.20 Defines the output frequency during brake opening delay to direction<br />

S2.<br />

Brake Stop Freq P2.3.21 When stopping the contact of the relay output ROB2 opens when the<br />

output frequency of drive goes below the value set in this parameter.<br />

ESR Point Freq P2.3.22 Defines ESR (field weakening) point frequency in percents of motor<br />

nominal frequency.<br />

ESR Point Volt P2.3.23 Defines ESR (field weakening) point voltage in percents of motor<br />

nominal voltage.<br />

IrAdd Motor P2.3.24 With small speeds and heavy load the hoist movement does not<br />

have enough voltage to produce sufficient torque. Raising the value<br />

of this parameter increases the voltage. Must not be changed.<br />

IrAdd Generator P2.3.25 If motor voltage at generator area is too high, reducing value of<br />

parameter decreases the voltage.<br />

0 - Max Freq S2, Hz<br />

0 - Max Freq S2, Hz<br />

0 - Max Freq S2, Hz<br />

0 – 250 %<br />

0 – 250 %<br />

0 – 200 %<br />

0 – 200 %<br />

Ramp Stretching P2.3.26 See Chapter "Ramp Stretching". Not used in hoisting 0 – 50 %<br />

Switching Frequency P2.3.27 Must not be changed from factory setting 3.6 kHz<br />

DeadTime Comp P2.3.28 Dead time compensation time delay. Parameter value does not tell<br />

the actual time used in compensation.<br />

DeadTime CurrLim P2.3.29 Parameter that is used to control the current waveform in dead time<br />

compensation.<br />

0 – 10000<br />

0 – 1000<br />

Brake Chopper P2.3.30 Defines when braking chopper is allowed to be activated.<br />

1 = Yes (Run)<br />

Always while drive is in ready state or only while running. 0 = Yes (Ready)<br />

G4. Monitoring<br />

G4.1 Parameter backup<br />

Load Default Par B4.1.1 Restores Default Parameters to Active Parameters from the Control<br />

Unit memory. Default Parameters are the parameters, which have<br />

been saved in the factory.<br />

32/79<br />

This document and the information contained herein, is the exclusive property of R&M <strong>Materials</strong> <strong>Handling</strong> Inc. and represents a non-public, confidential and proprietary<br />

trade secret that may not be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of R&M<br />

<strong>Materials</strong> <strong>Handling</strong> Inc. Copyright © (2005) R&M <strong>Materials</strong> <strong>Handling</strong> Inc. All rights reserved.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!