2.3.6 Du/dt filters<br />

If inverter is not mounted on the crane, there has to be du/dt filter at motor supply. Also if total motor<br />

cable length (sum of motor cables ) is over 100m with 002 –005 or over 200m with 007 –055, there has<br />

to be du/dt filter at motor supply.<br />

Power class Platthaus du/dt filter Length (mm) Width (mm) Height (mm) Weight (kg) ID<br />

002 – 003 ULC-910-920 100 110 180 1.2 52306553<br />

004 – 005 ULC-914-931 125 110 200 3 52306554<br />

007 – 018 ULC-918-951 155 125 225 7 52306555<br />

022 – 045 ULC-923-927 190 135 260 12 52306556<br />

055 ULC-942-1044 240 175 310 22 52306557<br />

! Du/dt filter should be as near inverter as possible<br />

! Note! All control cables must be placed as far from the motor and braking resistor cables as<br />

possible.<br />

2.4 Signal cabling<br />

2.4.1 Shielded signal cable<br />

It's recommended to use twisted pair and braided shielded signal cables. Foil type shield is not sufficient<br />

enough in crane applications because of poor mechanical durability. Cable insulation material effects to<br />

cable capacitance. Recommended cable capacitance between signal-signal and signal-ground is equal<br />

or less than 100pF/m (31pF/ft).<br />

It is not recommended to use shielded flat cable, because its capacitance is extremely high and this may<br />

cause high frequency interference.<br />

2.4.2 Reference signals<br />

Shielded round cables must be used for analog reference signals. The shield is to be grounded only at<br />

one end of the cable.<br />

2.4.3 Sensor bearing<br />

The cable for the sensor bearings must be shielded round cable and grounded 360° at both ends.<br />

2.4.4 Encoder<br />

The encoder connections may be split into two cables, then the signal conductors (4pcs) should go<br />

together in one cable and the supply and common (+24V/0V) together in another cable. The encoder<br />

cable(s) must be shielded round cable(s) and grounded 360° at both ends.<br />

! Note! All shielded cables must be placed as far from the motor cables as possible (>20cm).<br />

Shielding must be continuous. The "pigtail" (= the end to be connected) of the shield should<br />

not be used, instead 360° grounding should be used to minimize disturbances.<br />

! If control cable length is over 100m (from transformer to inverter) or inverter is not mounted<br />

on the crane, make sure that Basic I/O board (Slot A) is at least revision 271G and I/O<br />

Extension board (Slot D) is at least revision 266H<br />

14/79<br />

This document and the information contained herein, is the exclusive property of R&M <strong>Materials</strong> <strong>Handling</strong> Inc. and represents a non-public, confidential and proprietary<br />

trade secret that may not be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of R&M<br />

<strong>Materials</strong> <strong>Handling</strong> Inc. Copyright © (2005) R&M <strong>Materials</strong> <strong>Handling</strong> Inc. All rights reserved.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!