3-Step PI-Regulator 431.011
3-Step PI-Regulator 431.011
3-Step PI-Regulator 431.011
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
3-<strong>Step</strong> <strong>PI</strong>-<strong>Regulator</strong><br />
<strong>431.011</strong><br />
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------<br />
• Temperature regulator with modulating output, <strong>PI</strong>-characteristic<br />
• Universal adjustable temperature limitation<br />
• Setpoint range for main and limitation function –15…+60°C<br />
For temperature regulation by controlling an actuator with reversible servomotor,<br />
particularly for regulation of the room temperature with limitation of the<br />
minimum supply air temperature, limitation of the maximum supply water temperature<br />
and others.<br />
Description<br />
The regulator has a three-step output with an electronic <strong>PI</strong>-feedback for driving<br />
an actuator with a reversible servomotor. It compares the set point with the actual<br />
temperature measured by the main sensor and drives the connected actuator<br />
stepwise until the deviation is within the thresholds. If the temperature measured<br />
by the limitation sensor reaches the adjusted minimum resp. maximum<br />
value, the limitation sensor takes over the regulation (absolute limitation).<br />
On the front, there are separate control knobs for main and limitation function,<br />
further LEDs indicating the actual command for warmer or colder.<br />
A setpoint remote control and an indicator for temperature indication are connectable<br />
to the device.<br />
Adjustment<br />
0<br />
-10<br />
20<br />
10 30<br />
°C<br />
Hauptsollwert<br />
10<br />
20<br />
40<br />
50<br />
60<br />
0<br />
K<br />
30<br />
Rückführung<br />
<strong>431.011</strong><br />
+<br />
–<br />
regel- und messtechnische apparate gmbh herrsching<br />
Tender description<br />
0<br />
20<br />
10 30<br />
40<br />
50<br />
-10<br />
60<br />
°C<br />
Begrenzungssollwert<br />
10<br />
20<br />
0<br />
K<br />
30<br />
Rückführung<br />
RAM 3-<strong>Step</strong> <strong>PI</strong>-<strong>Regulator</strong> type <strong>431.011</strong>.<br />
Electronic temperature regulator with universal limitation,<br />
LEDs and connectivity for remote controls and indicators.<br />
Plastic case 70x100x105mm for rail and panel mounting.<br />
Setpoint ranges –15…+60°C.<br />
Power supply 230V~, enclosure rating IP 40.<br />
If a setpoint remote control is connected, the main setpoint (“Hauptsollwert”) of<br />
the regulator has to be set to 20°C.<br />
Adjustment of the limitation<br />
The limitation setpoint (“Begrenzungssollwert”) defines the operating point of<br />
the limitation. Function and mode are chosen by the slide switch "Begrenzung"<br />
inside the device:<br />
Min – Max ... function as minimum or maximum limitation,<br />
direkt – invers ... mode of limitation direct - inverse.<br />
The required setting depends on the temperature change at the limitation sensor<br />
in comparison with the change at the main sensor. If the temperature at the<br />
main sensor increases after driving the actuator and the temperature<br />
at the limitation sensor also increases - direct mode,<br />
at the limitation sensor decreases - inverse mode.<br />
Adaption to the controlled system<br />
The feedback (“Rückführung”, P-band Xp of the <strong>PI</strong>-feedback) serves for stabilization<br />
of the main resp. limitation loop.<br />
Reference value for room and exhaust air regulation about Xp=20…30K, for<br />
supply air and supply water regulation (limitation) about Xp=10K.<br />
(These reference values are valid for ~2min motor running time. For longer running<br />
times corresponding lower values are preferable.)<br />
LED display<br />
<strong>Regulator</strong> requires higher temperature<br />
(more heating or less cooling)<br />
<strong>Regulator</strong> requires lower temperature<br />
(less heating or more cooling)<br />
Technical data<br />
Power supply<br />
230V±10%, 50/60Hz, ca. 3VA<br />
Ambient temperature 0…+60°C<br />
Enclosure rating IP 40, protective insulation<br />
Weight<br />
570g<br />
Adjustment ranges<br />
- Main set point –15...+60°C<br />
- Feedback Xp=0…30 K<br />
- Limitation set point –15...+60°C<br />
- Feedback Xp=0…30 K<br />
Output<br />
floating contact<br />
- Switching capacity 250V/500VA inductive<br />
- Switching threshold ±0.3K<br />
- Feedback <strong>PI</strong>, reset time Tn = 10 min<br />
Dimension drawing<br />
Mounting<br />
The device is intended for wall and panel mounting.<br />
Wall mounting is possible by snapping on a 35mm assembly<br />
rail or with screws. For panel mounting an accessory<br />
type 999.401 is required.<br />
11.01.07 ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------<br />
RAM Regel- und Messtechnische Apparate GmbH, Herrsching
<strong>431.011</strong> External connection<br />
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------<br />
Basic circuit (fig. 1)<br />
Output optionally for heating (warmer = open) or cooling<br />
(colder = open).<br />
Select the suitable version of the temperature sensor<br />
from the RAM sensor program and complete the part<br />
number.<br />
To deactivate the limitation, bridge terminal 18 -19, if<br />
“Min” is chosen or disconnect the limitation sensor, if<br />
“Max” is chosen (setting of the limitation setpoint is arbitrary).<br />
Options<br />
Connection of setpoint remote control and indicator<br />
(fig. 2)<br />
Digital indicators have to be connected according to<br />
data sheet series 242/fig. 3.<br />
Circuits with time program<br />
Lowering the setpoint at night with a timer (fig. 3)<br />
The day setpoint is adjusted on the regulator or on a<br />
remote control (acc. to fig. 2).<br />
Further circuit options:<br />
- Separate remote controls for day and night setpoint<br />
switched by a timer, see data sheet series 230.<br />
- Remote setting in the room and activation of the<br />
lowering at night by a timer, see data sheet 238.<br />
200/211.<br />
Special versions<br />
3-step <strong>PI</strong>-<strong>Regulator</strong> <strong>431.011</strong>.902<br />
with summer compensation (fig. 4)<br />
Continuous set point increase depending on the outdoor<br />
temperature, starting point +20°C, gradient 0.5K<br />
increase per 1K increase of the outdoor temperature.<br />
Select the suitable version of the temperature sensor<br />
from the RAM sensor program and complete the part<br />
number.<br />
If required an indicator for the outdoor temperature is<br />
connectable.<br />
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------<br />
RAM Regel- und Messtechnische Apparate GmbH, Herrsching