Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>LOGO</strong>!<strong>Power</strong><br />
<strong>LOGO</strong>!<strong>Power</strong> 24 V<br />
■ Overview<br />
■ Application<br />
<strong>LOGO</strong>!<strong>Power</strong> <strong>supplies</strong> are primary switched-mode <strong>power</strong> <strong>supplies</strong> that are optimized to the<br />
<strong>LOGO</strong>! logic modules in terms of functionality and design. With the wide input range of 85 V to<br />
264 V AC, radio interference level B and assembly option in built-in miniature distribution boards,<br />
they can be used universally in a diverse range of applications in the low-end performance range.<br />
13<br />
■ Technical specifications<br />
<strong>Power</strong> supply, type 24 V/1.3 A 24 V/2.5 A 24 V/4 A<br />
Order No. 6EP1 331-1SH02 6EP1 332-1SH42 6EP1 332-1SH51<br />
Input Single-phase AC Single-phase AC Single-phase AC<br />
Rated voltage V in rated<br />
100 to 240 V AC<br />
100 to 240 V AC<br />
100 to 240 V AC<br />
wide-range input<br />
wide-range input<br />
wide-range input<br />
Voltage range 85 to 264 V AC 85 to 264 V AC 85 to 264 V AC<br />
Overvoltage strength 2.3 x V in rated /1.3 ms 2.3 x V in rated /1.3 ms 2.3 x V in rated /1.3 ms<br />
Mains buffering at I out rated > 40 ms at V in = 187 V > 40 ms at V in = 187 V > 40 ms at V in = 187 V<br />
Rated line frequency; range 50/60 Hz; 47 to 63 Hz 50/60 Hz; 47 to 63 Hz 50/60 Hz; 47 to 63 Hz<br />
Rated current I in rated 0.7 to 0.35 A 1.22 to 0.66 A 1.95 to 0.97 A<br />
Inrush current limitation (+25 °C) < 15 A < 30 A < 30 A<br />
I 2 t < 0.8 A 2 s < 3 A 2 s < 2.5 A 2 s<br />
Integrated line-side fuse Internal Internal Internal<br />
Recommended circuit-breaker From 16 A Characteristic B or From 16 A Characteristic B or From 16 A Characteristic B or<br />
(IEC 898) in mains supply line from 10 A Characteristic C<br />
from 10 A Characteristic C<br />
from 10 A Characteristic C<br />
Output Stabilized, floating direct voltage Stabilized, floating direct voltage Stabilized, floating direct voltage<br />
Rated voltage V out rated 24 V DC 24 V DC 24 V DC<br />
Total tolerance, static ± 3 % ± 3 % ± 3 %<br />
• Static mains compensation Approx. 0.1 % Approx. 0.1 % Approx. 0.1 %<br />
• Static load compensation Approx. 1.5 % Approx. 1.5 % Approx. 1.5 %<br />
Residual ripple<br />
< 200 mV pp < 200 mV pp < 200 mV pp<br />
(clock frequency approx. 90 kHz)<br />
Spikes (bandwidth approx. 20 MHz) < 300 mV pp < 300 mV pp < 300 mV pp<br />
Setting range 22.2 to 26.4 V 22.2 to 26.4 V 22.2 to 26.4 V<br />
Status display<br />
Green LED for output voltage Green LED for output voltage Green LED for output voltage<br />
OK<br />
OK<br />
OK<br />
<strong>Power</strong> ON/OFF behavior No overshoot of V out (soft start) No overshoot of V out (soft start) No overshoot of V out (soft start)<br />
Starting delay/voltage rise < 0.5 s/typ. 15 ms < 0.5 s/typ. 10 ms < 0.5 s/typ. 35 ms<br />
Rated current I out rated 1.3 A 2.5 A 4 A<br />
Current range up to +55 °C 0 to 1.3 A 0 to 2.5 A 0 to 4 A<br />
Parallel connection for increased Yes Yes Yes<br />
output<br />