<strong>SITOP</strong> <strong>power</strong> · Standard 24 V<br />
Uninterruptible <strong>power</strong> <strong>supplies</strong><br />
Battery module 7 Ah<br />
■ Overview<br />
• Battery for DC UPS module 6 A and 15 A and DC UPS module<br />
40 A<br />
• Contains two maintenance-free, sealed lead-acid batteries<br />
from the same batch fitted in a holder and connected in series<br />
• Completely prewired with battery fuse holder and terminals<br />
• Accessory pack with FK2 spare fuses 15 A and 20 A<br />
• Low self-discharge rate of approx. 3 % per month (at +20 °C)<br />
■ Technical specifications<br />
Battery module 7 Ah<br />
Order No.<br />
6EP1 935-6ME21<br />
Battery type, charging current/ Maintenance-free, sealed leadacid<br />
batteries 1)<br />
charging voltage<br />
Recommended end-of-charge voltage (standby use)<br />
• For +25 °C battery temperature 27.0 V DC<br />
• For other battery temperatures 27.8 V for +10 °C;<br />
27.3 V for +20 °C;<br />
26.8 V for +30 °C;<br />
26.7 V for +35 °C;<br />
26.6 V for +40 °C<br />
Recommended charging current Max. 1.75 A<br />
Protection<br />
Short-circuit protection<br />
Battery fuse 15 A/32 V<br />
(FK2 flat fuse + holder)<br />
Battery protection<br />
Valve control<br />
Safety<br />
Protective class<br />
Class III<br />
UL/cUL (CSA) approval<br />
UL/cUL recognized (UL1778,<br />
CSA 22.2 No. 107.1-95),<br />
File E219627<br />
Degree of protection (EN 60529) IP00<br />
Operating specifications<br />
Ambient temperature +5 to +40 °C<br />
Transportation and storage temperature<br />
range<br />
-20 to +50 °C<br />
Self-discharge rate<br />
Approx. 3 % per month at<br />
a battery temperature of 20 °C<br />
Service life<br />
The service life of the chemical lead-acid batteries (reduction to 50 % of<br />
original capacity) depends on the battery temperature as follows:<br />
At +20 °C<br />
Approx. 4 years<br />
At +25 °C<br />
Approx. 3.5 years<br />
At +30 °C<br />
Approx. 3 years<br />
At +35 °C<br />
Approx. 2.5 years<br />
At +40 °C<br />
Approx. 2 years<br />
At +45 °C<br />
Approx. 1.5 years<br />
At +50 °C<br />
Approx. 1 year<br />
Mechanical specifications<br />
Connection 1 terminal each for 0.08 to 4 mm 2<br />
for + BAT - BAT<br />
Supplied accessories<br />
Accessory pack with FK2 spare<br />
fuses 15 A and 20 A<br />
Dimensions (W x H x D) in mm Approx. 186 x 168 x 121<br />
Weight<br />
Approx. 6.0 kg<br />
Mounting<br />
Can be screwed on level surface<br />
(Keyhole mounting for hanging in<br />
M4 screws)<br />
9<br />
1) For storage, installation and operation of the lead-acid batteries, the<br />
appropriate DIN/VDE regulations or the country-specific directives (e.g.<br />
VDE 0510 Part 2/EN 50272-2) must be observed.The battery location must<br />
be sufficiently ventilated, potential ignition sources must be at least 50 cm<br />
away.<br />
Siemens KT<strong>10.1</strong> · <strong>2004</strong> 9/17