<strong>SITOP</strong> <strong>power</strong> · Standard 24 V<br />
Uninterruptible <strong>power</strong> <strong>supplies</strong><br />
Battery module 2.5 Ah<br />
■ Overview<br />
• High-temperature battery for DC UPS module 6 A and 15 A<br />
• Contains two maintenance-free, sealed chemical lead-acid<br />
batteries from the same batch fitted in a holder and connected<br />
in series<br />
• Completely prewired with battery fuse holder and terminals<br />
• Low self-discharge rate of approx. 3 % per month (at +20 °C)<br />
■ Technical specifications<br />
Battery module 2.5 Ah<br />
Order No.<br />
6EP1 935-6MD31<br />
Battery type, charging current/ Maintenance-free chemical<br />
charging voltage<br />
lead-acid batteries 1)<br />
Recommended end-of-charge voltage (standby use)<br />
• For +25 °C battery temperature 27.7 V DC<br />
• For other battery temperatures 29.0 V for -10 °C;<br />
28.6 V for 0 °C;<br />
28.3 V for +10 °C;<br />
27.9 V for +20 °C;<br />
27.5 V for +30 °C;<br />
27.2 V for +40 °C;<br />
26.8 V for +50 °C;<br />
26.4 V for +60 °C<br />
Recommended charging current Max. 5 A<br />
Protection<br />
Short-circuit protection<br />
Battery fuse 15 A/32 V<br />
(FK2 flat fuse + holder)<br />
Battery protection<br />
Valve control<br />
Safety<br />
Protective class<br />
Class III<br />
UL/cUL (CSA) approval<br />
UL/cUL recognized (UL1778,<br />
CSA 22.2 No. 107.1-95),<br />
File E219627<br />
Degree of protection (EN 60529) IP00<br />
Operating specifications<br />
Ambient temperature range -40 to +60 °C with natural<br />
convection<br />
Transportation and storage temperature<br />
range<br />
-40 to +60 °C<br />
Self-discharge rate<br />
Approx. 3 % per month at a<br />
battery temperature of 20 °C<br />
(increased value at higher temperature)<br />
Service life<br />
The service life of the chemical lead-acid batteries (reduction to 80 % of<br />
original capacity) depends on the battery temperature as follows:<br />
At +15 °C<br />
Approx. 19 years<br />
At +20 °C<br />
Approx. 13 years<br />
At +25 °C<br />
Approx. 9 years<br />
At +30 °C<br />
Approx. 7 years<br />
At +35 °C<br />
Approx. 5 years<br />
At +40 °C<br />
Approx. 3 years<br />
At +45 °C<br />
Approx. 2 years<br />
At +50 °C<br />
Approx. 1.5 years<br />
At +60 °C<br />
Approx. 1 year<br />
Mechanical specifications<br />
Connection<br />
1 terminal each for 0.08 to<br />
2.5 mm 2 for + BAT and - BAT<br />
Supplied accessories<br />
Accessory pack with FK2 fuse<br />
15 A<br />
Dimensions (W x H x D) in mm Approx. 265 x 151 x 91<br />
Weight<br />
Approx. 3.8 kg<br />
Mounting<br />
Snap-mounting on DIN rail<br />
EN 50022-35x15/7.5 or keyhole<br />
mounting for hanging in M4<br />
screws<br />
9<br />
1) For storage, installation and operation of the lead-acid batteries, the<br />
appropriate DIN/VDE regulations or the country-specific directives (e.g.<br />
VDE 0510 Part 2/EN 50272-2) must be observed. The battery location must<br />
be sufficiently ventilated, potential ignition sources must be at least 50 cm<br />
away.<br />
Siemens KT<strong>10.1</strong> · <strong>2004</strong> 9/15