Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>SITOP</strong> <strong>power</strong> · Standard 24 V<br />
Uninterruptible <strong>power</strong> <strong>supplies</strong><br />
DC UPS module 40 A<br />
■ Overview<br />
• Mounting depth only approx. 65 mm<br />
• Rated output <strong>power</strong> 480 W with one battery module, 960 W with<br />
two battery modules<br />
• Extremely high efficiency of approx. 99% as result of patented<br />
circuit concept<br />
• Immediate electronic connection of battery as soon as the consumer<br />
voltage or the voltage present between the L+/M terminals<br />
of the DC UPS module falls below a value of 22.5 V DC.<br />
The consumer voltage only drops to 22 V DC for a maximum of<br />
1 ms.<br />
• High electronically limited peak currents (120 A for approx.<br />
12 ms, up to 40 A for several minutes depending on the battery<br />
capacity) are automatically delivered in the event of increased<br />
load current requirements (e.g. when switching on incandescent<br />
lamps, contactors with DC autotransformer winding,<br />
DC motors, DC/DC converters, electronic modules with high<br />
input capacitance). To achieve this, at least two battery modules<br />
of 7 Ah or more must be connected in parallel.<br />
• Following a <strong>power</strong> failure, the battery module is automatically<br />
disconnected from the consumers electronically and rapidly<br />
recharged with a constant current of 2 A (V/I characteristic with<br />
27.3 V end-of-charge voltage).<br />
• Signalling<br />
- Green LED/yellow LED and floating changeover contact for<br />
mains/battery mode<br />
- Red LED and floating changeover contact for buffer readiness<br />
(LED off)/ alarm (LED on)<br />
■ Integration<br />
Mains Main switch <strong>Power</strong> supply DC UPS module Load<br />
24 V<br />
DC UPS module 40<br />
24 V<br />
<strong>SITOP</strong> <strong>power</strong><br />
3 AC<br />
10 to 40 A<br />
Aux. contact<br />
ON/OFF<br />
Message: mains or<br />
buffer mode<br />
(floating changeover<br />
contact)<br />
Message: buffer<br />
readiness<br />
or alarm/prewarning<br />
prior to switching-off<br />
of battery<br />
9<br />
24 V battery module<br />
G_KT01_EN_00159<br />
Block diagram: Configuration of uninterruptible <strong>SITOP</strong> <strong>power</strong> supply 40 A<br />
Siemens KT<strong>10.1</strong> · <strong>2004</strong> 9/11