Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>SITOP</strong> <strong>power</strong> · Standard 24 V<br />
Uninterruptible <strong>power</strong> <strong>supplies</strong><br />
DC UPS module 6 A and 15 A<br />
DC<br />
DC<br />
DC UPS module 6<br />
DC UPS module 15<br />
battery<br />
X1.7 +Bat<br />
27-<br />
18.5 V DC<br />
X1.8 -Bat<br />
<strong>SITOP</strong><br />
<strong>power</strong><br />
supply<br />
L+ X1.1<br />
Input V in<br />
24 V DC<br />
M X1.2<br />
<strong>power</strong> section<br />
X1.3 L+<br />
X1.5 L+<br />
output<br />
V out<br />
X1.4 M<br />
X1.6 M<br />
load<br />
serial<br />
X3.1-9<br />
interface<br />
only 6EP1931-2DC31<br />
and 6EP1931-2EC31<br />
control<br />
X2.1<br />
X2.3<br />
X2.2<br />
X2.4<br />
X2.6<br />
X2.5<br />
X2.7<br />
X2.8<br />
Bat<br />
24 V DC o.k.<br />
alarm<br />
readiness<br />
charge 85%<br />
green yellow red green<br />
1<br />
X2.9 operating state battery<br />
X2.10 M On/Off<br />
+2 V<br />
+1 V<br />
+0.5 V<br />
+1 V<br />
+0.5 V<br />
+0.2 V<br />
+0.2 V<br />
+0.1 V<br />
connection threshold<br />
+22 V fixed<br />
end-of-charge<br />
voltage<br />
+26.3 V fixed<br />
operating elements<br />
charging current * 1<br />
set time/max. time<br />
+320 s<br />
+160 s<br />
+ 80 s buffering time<br />
+ 40 s<br />
+ 20 s +5 s fixed<br />
+ 10 s<br />
interruption V out<br />
operating state battery<br />
On/Off<br />
*1: charging current 0.2 A or 0.4 A for 6EP1931-2DC../0.35 A or 0.7 A for 6EP1931-2EC..<br />
G_KT01_EN_00226<br />
9/4<br />
Siemens KT<strong>10.1</strong> · <strong>2004</strong>