31.05.2014 Views

Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004

Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004

Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>SITOP</strong> <strong>power</strong> · Standard 24 V<br />

Additional components<br />

■ Overview<br />

<strong>SITOP</strong> select<br />

■ Application<br />

The diagnosis module is used together with 24 V <strong>power</strong> supply units to divide the load current between<br />

several branch circuits and to monitor the individual currents. Faults in the individual circuits<br />

resulting from an overload or short-circuit are detected and switched off selectively, and other load<br />

current paths therefore remain unaffected by the fault. This results in rapid fault diagnostics, and<br />

downtimes are minimized.<br />

8<br />

■ Technical specifications<br />

Type<br />

Module 4 x 10 A<br />

Order No.<br />

6EP1 961-2BA00<br />

Input<br />

DC voltage<br />

Rated voltage V in rated<br />

24 V DC<br />

Voltage range<br />

22 to 30 V<br />

Overvoltage strength<br />

35 V; 100 ms<br />

Output<br />

DC voltage<br />

Rated voltage V out rated<br />

V out - 0.5 V<br />

Total tolerance/<br />

Corresponding to the input voltage<br />

residual ripple<br />

Number of output channels 4<br />

Rated current<br />

10 A per channel<br />

I out rated up to +60 °C<br />

Setting range<br />

2 to 10 A per channel<br />

Parallel connection of several Not permissible<br />

channels<br />

Efficiency<br />

Efficiency at V out rated , I out rated Approx. 97 %<br />

<strong>Power</strong> loss at V out rated , I out rated Approx. 30 W<br />

Switch-off characteristic per<br />

channel<br />

Overcurrent<br />

I out = 1.0 to 1.3 x set value, switch-off after approx. 5 s<br />

Current limitation<br />

I out = 1.35 x set value, switch-off after approx. 50 to 100 ms<br />

Immediate switch-off<br />

I out > set value and V in < 20 V<br />

Reset<br />

Using keys on module<br />

Protection and monitoring<br />

Line protection<br />

Electronic; additionally possible via accessible FK2 blade-type fuse (equipped when delivered with 15 A<br />

fuse) per channel<br />

Status displays<br />

Two-color LED per channel, green for output switched through, red for output switched off<br />

Signaling contact<br />

Common signal contact (NO contact)<br />

Safety<br />

Protective class<br />

Class III<br />

Degree of protection (EN 60529) IP20<br />

TÜV test<br />

Yes<br />

CE marking<br />

Yes<br />

UL/cUL (CSA) approval Yes, cULus listed (UL 508, CSA 22.2 No. 14-M91), File E197259;<br />

cURus recognized (UL 60950, CSA 22.2 No. 60950), File E151273<br />

EMC<br />

Interference emission<br />

EN 55022 Class B<br />

Interference immunity EN 61000-6-2<br />

Operating specifications<br />

Ambient temperature range 0 to +60 °C with natural convection<br />

Transportation and storage<br />

-25 to +85 °C<br />

temperature range<br />

Humidity rating<br />

Climatic class 3K3 acc. to EN 60721, no condensation<br />

8/4<br />

Siemens KT<strong>10.1</strong> · <strong>2004</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!