Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004 Power supplies SITOP power LOGO!Power Catalog K T 10.1 2004
Technical information and configuration Fusing of the output circuit 24 V DC, selectivity ■ Miniature circuit-breakers in 24 V DC circuits which are powered by SITOP power supply units Technical specifications Type 20 A 40 A Order No. 6EP1 436-2BA00 6EP1 437-2BA10 Input Three-phase Single-phase, two-phase Rated voltage V in rated 400-500 V 3 AC 400-500 V AC Output Stabilized, floating direct voltage Stabilized, floating direct voltage Rated voltage V out rated 24 V DC 24 V DC Rated current I out rated 20 A 40 A Dyn. V/I with short-circuit in operation, typ. Approx. 30 A constant current 70 A for 600 ms Tripping of output m.c.b The following are approximately available for selective tripping in practice SITOP, dyn. V/I - 50% I out rated , typ. 20 A (without interruption) 50 A for 600 ms CBs to IEC 898, type 5SY4 1.., selectively trippable in approx. 12 ms 1 A Type A (trips at 5 A DC after typ. 12 ms) 1 A Type C (trips at 14 A DC after typ. 12 ms) 1.6 A Type A (trips at 8 A DC after typ. 12 ms) - 1.6 A Type C (trips at 22.4 A DC after typ. 12 ms) 2 A Type A (trips at 10 A DC after typ. 12 ms) - 2 A Type C (trips at 28 A DC after typ. 12 ms) 3 A Type A (trips at 15 A DC after typ. 12 ms) - 3 A Type C (trips at 42 A DC after typ. 12 ms) 4 A Type A (trips at 20 A DC after typ. 12 ms) - 6 A Type A (trips at 30 A DC after typ. 12 ms) - 6 A Type B (trips at 42 A DC after typ. 12 ms) - 8 A Type A (trips at 40 A DC after typ. 12 ms) - 10 A Type A (trips at 50 A DC after typ. 12 ms) Siemens CB terminals, Type 8WA1 011..., selectively trippable in approx. 12 ms 2 A Order No. 8WA1 011-1SF25 (trips at 7.6 A DC after max. 12 ms) 4 A Order No. 8WA1 011-1SF26 (trips at 15.2 A DC after max. 12 ms) - 6 A Order No. 8WA1 011-1SF27 (trips at 22.8 A DC after max. 12 ms) - 10 A Order No. 8WA1 011-1SF28 (trips at 38 A DC after max. 12 ms) 14 14/20 Siemens KT10.1 · 2004
Technical information and configuration Fusing of the output circuit 24 V DC, selectivity ■ Miniature circuit-breakers in 24 V DC circuits which are powered by SITOP power supply units Technical specifications Type 20 A 40 A Order No. 6EP1 436-3BA00 (6EP1 336-3BA00) 6EP1 437-3BA00 (6EP1 337-3BA00) Input Rated voltage V in rated Three-phase (single-phase) 400-500 V 3 AC (120/230 V AC) Three-phase (single-phase) 400-500 V 3 AC (120/230 V AC) Output Stabilized, floating direct voltage Stabilized, floating direct voltage Rated voltage V out rated 24 V DC 24 V DC Rated current I out rated 20 A 40 A Dyn. V/I with short-circuit in operation, typ. Approx. 60 A for 25 ms Approx. 120 A for 25 ms Tripping of output m.c.b The following are approximately available for selective tripping in practice SITOP, dyn. V/I - 50% I out rated , typ. 50 A for 25 ms 100 A for 25 ms CBs to IEC 898, type 5SY4 1.., selectively trippable in approx. 12 ms 1 A Type A (trips at 5 A DC after typ. 12 ms) 1 A Type C (trips at 14 A DC after typ. 12 ms) 1.6 A Type A (trips at 8 A DC after typ. 12 ms) 1.6 A Type C (trips at 22.4 A DC after typ. 12 ms) 2 A Type A (trips at 10 A DC after typ. 12 ms) 2 A Type C (trips at 28 A DC after typ. 12 ms) 3 A Type A (trips at 15 A DC after typ. 12 ms) 3 A Type C (trips at 42 A DC after typ. 12 ms) 4 A Type A (trips at 20 A DC after typ. 12 ms) - 4 A Type C (trips at 56 A DC after typ. 12 ms) 6 A Type A (trips at 30 A DC after typ. 12 ms) 6 A Type B (trips at 42 A DC after typ. 12 ms) - 6 A Type C (trips at 84 A DC after typ. 12 ms) 8 A Type B (trips at 40 A DC after typ. 12 ms) 10 A Type A (trips at 50 A DC after typ. 12 ms) - 10 A Type B (trips at 70 A DC after typ. 12 ms) - 13 A Type A (trips at 65 A DC after typ. 12 ms) - 13 A Type B (trips at 91 A DC after typ. 12 ms) - 16 A Type A (trips at 80 A DC after typ. 12 ms) - 20 A Type A (trips at 100 A DC after typ. 12 ms) Siemens CB terminals, Type 8WA1 011..., selectively trippable in approx. 12 ms 2 A Order No. 8WA1 011-1SF25 (trips at 7.6 A DC after max. 12 ms) 4 A Order No. 8WA1 011-1SF26 (trips at 15.2 A DC after max. 12 ms) 6 A Order No. 8WA1 011-1SF27 (trips at 22.8 A DC after max. 12 ms) 10 A Order No. 8WA1 011-1SF28 (trips at 38 A DC after max. 12 ms) 14 Siemens KT10.1 · 2004 14/21
- Page 67 and 68: SITOP power · Standard 24 V Uninte
- Page 69 and 70: SITOP power · Standard 24 V Uninte
- Page 71 and 72: SITOP power · Standard 24 V Uninte
- Page 73 and 74: SITOP power · Standard 24 V Uninte
- Page 75 and 76: SITOP power · Standard 24 V Uninte
- Page 77 and 78: SITOP power Alternative voltages 10
- Page 79 and 80: SITOP power Alternative voltages
- Page 81 and 82: SITOP power AS interface power supp
- Page 83 and 84: Power supply, type 2.4 A 7 A Order
- Page 85 and 86: SITOP power Customized 12 12/2 Desc
- Page 87 and 88: SITOP power Customized ■ FAX repl
- Page 89 and 90: LOGO!Power 13 13/2 LOGO!Power 5 V 1
- Page 91 and 92: LOGO!Power LOGO!Power 5 V Power sup
- Page 93 and 94: LOGO!Power LOGO!Power 12 V Power su
- Page 95 and 96: LOGO!Power LOGO!Power 15 V Power su
- Page 97 and 98: LOGO!Power LOGO!Power 24 V Power su
- Page 99 and 100: Technical information and configura
- Page 101 and 102: Technical information and configura
- Page 103 and 104: Technical information and configura
- Page 105 and 106: Technical information and configura
- Page 107 and 108: Technical information and configura
- Page 109 and 110: Technical information and configura
- Page 111 and 112: Technical information and configura
- Page 113 and 114: Technical information and configura
- Page 115 and 116: Technical information and configura
- Page 117: Technical information and configura
- Page 121 and 122: Dimension drawings 15 SITOP power N
- Page 123 and 124: Dimension drawings SITOP power Sing
- Page 125 and 126: Dimension drawings SITOP power Sing
- Page 127 and 128: Dimension drawings SITOP power Sing
- Page 129 and 130: Dimension drawings SITOP power Addi
- Page 131 and 132: Dimension drawings SITOP power Unin
- Page 133 and 134: Dimension drawings SITOP power Alte
- Page 135 and 136: Dimension drawings LOGO!Power ■ D
- Page 137 and 138: Appendix 16 16/2 SITOP contact pers
- Page 139 and 140: Appendix SITOP contact persons ■
- Page 141 and 142: Appendix SITOP contact persons ■
- Page 143 and 144: Appendix Siemens contacts worldwide
- Page 145 and 146: Appendix Indexes ■ Order No. inde
- Page 147 and 148: Appendix Customer Support Our Servi
- Page 149 and 150: Appendix Notes 16 Siemens KT10.1 ·
- Page 151 and 152: Catalogs of the Automation and Driv
Technical information and configuration<br />
Fusing of the output circuit 24 V DC,<br />
selectivity<br />
■ Miniature circuit-breakers in 24 V DC circuits which are <strong>power</strong>ed by <strong>SITOP</strong> <strong>power</strong> supply units<br />
Technical specifications<br />
Type 20 A 40 A<br />
Order No. 6EP1 436-2BA00 6EP1 437-2BA10<br />
Input Three-phase Single-phase, two-phase<br />
Rated voltage V in rated 400-500 V 3 AC 400-500 V AC<br />
Output Stabilized, floating direct voltage Stabilized, floating direct voltage<br />
Rated voltage V out rated 24 V DC 24 V DC<br />
Rated current I out rated 20 A 40 A<br />
Dyn. V/I with short-circuit in operation, typ. Approx. 30 A constant current 70 A for 600 ms<br />
Tripping of output m.c.b<br />
The following are approximately available for selective tripping in practice<br />
<strong>SITOP</strong>, dyn. V/I - 50% I out rated , typ. 20 A (without interruption) 50 A for 600 ms<br />
CBs to IEC 898, type 5SY4 1.., selectively<br />
trippable in approx. 12 ms<br />
1 A Type A (trips at 5 A DC after typ. 12 ms)<br />
1 A Type C (trips at 14 A DC after typ. 12 ms)<br />
1.6 A Type A (trips at 8 A DC after typ. 12 ms)<br />
- 1.6 A Type C (trips at 22.4 A DC after typ. 12 ms)<br />
2 A Type A (trips at 10 A DC after typ. 12 ms)<br />
- 2 A Type C (trips at 28 A DC after typ. 12 ms)<br />
3 A Type A (trips at 15 A DC after typ. 12 ms)<br />
- 3 A Type C (trips at 42 A DC after typ. 12 ms)<br />
4 A Type A (trips at 20 A DC after typ. 12 ms)<br />
- 6 A Type A (trips at 30 A DC after typ. 12 ms)<br />
- 6 A Type B (trips at 42 A DC after typ. 12 ms)<br />
- 8 A Type A (trips at 40 A DC after typ. 12 ms)<br />
- 10 A Type A (trips at 50 A DC after typ. 12 ms)<br />
Siemens CB terminals, Type 8WA1 011...,<br />
selectively trippable in approx. 12 ms<br />
2 A Order No. 8WA1 011-1SF25 (trips at 7.6 A DC after max. 12 ms)<br />
4 A Order No. 8WA1 011-1SF26 (trips at 15.2 A DC after max. 12 ms)<br />
- 6 A Order No. 8WA1 011-1SF27 (trips at<br />
22.8 A DC after max. 12 ms)<br />
- 10 A Order No. 8WA1 011-1SF28 (trips at<br />
38 A DC after max. 12 ms)<br />
14<br />
14/20<br />
Siemens KT<strong>10.1</strong> · <strong>2004</strong>