Technical information and configuration<br />
■ Miniature circuit-breakers in 24 V DC circuits which are <strong>power</strong>ed by <strong>SITOP</strong> <strong>power</strong> supply units<br />
Fusing of the output circuit 24 V DC,<br />
selectivity<br />
Technical specifications<br />
Type 5 A 10 A<br />
Order No. 6EP1 333-3BA00 6EP1 334-3BA00<br />
Input Single-phase, two-phase Single-phase, two-phase<br />
Rated voltage V in rated 120/230-500 V AC 120/230-500 V AC<br />
Output Stabilized, floating direct voltage Stabilized, floating direct voltage<br />
Rated voltage V out rated 24 V DC 24 V DC<br />
Rated current I out rated 5 A 10 A<br />
Dyn. V/I with short-circuit in operation, typ. 15 A for 25 ms 30 A for 25 ms<br />
Tripping of output m.c.b<br />
The following are approximately available for selective tripping in practice<br />
<strong>SITOP</strong>, dyn. V/I - 50% I out rated , typ. 12.5 A for 25 ms 25 A for 25 ms<br />
CBs to IEC 898, type 5SY4 1.., selectively<br />
trippable in approx. 12 ms<br />
1 A Type A (trips at 5 A DC after typ. 12 ms)<br />
- 1 A Type C (trips at 14 A DC after typ. 12 ms)<br />
1.6 A Type A (trips at 8 A DC after typ. 12 ms)<br />
- 1.6 A Type C (trips at 22.4 A DC after typ. 12 ms)<br />
2 A Type A (trips at 10 A DC after typ. 12 ms)<br />
- 3 A Type A (trips at 15 A DC after typ. 12 ms)<br />
- 4 A Type A (trips at 20 A DC after typ. 12 ms)<br />
Siemens CB terminals, Type 8WA1 011..., 2 A Order No. 8WA1 011-1SF25 (trips at 7.6 A DC after max. 12 ms)<br />
selectively trippable in approx. 12 ms<br />
- 4 A Order No. 8WA1 011-1SF26 (trips at<br />
15.2 A DC after max. 12 ms)<br />
- 6 A Order No. 8WA1 011-1SF27 (trips at<br />
22.8 A DC after max. 12 ms)<br />
in 20 ms<br />
4 A Order No. 8WA1 011-1SF26 (trips at<br />
10.7 A DC after max. 20 ms)<br />
-<br />
14<br />
Siemens KT<strong>10.1</strong> · <strong>2004</strong> 14/19