• Plumbing fixture counts <strong>for</strong> public, staff, <strong>and</strong> patients, in accordance with the Cali<strong>for</strong>nia<br />

Plumbing Code requirements;<br />

• <strong>Project</strong> construction phasing <strong>of</strong> other work sequences that affect the project operations or<br />

impact code compliance;<br />

• Other work not included in the project <strong>and</strong> carried out under other permits if it affects the<br />

project;<br />

• Local zoning conditions <strong>of</strong> approval related to the project;<br />

• Parking counts, as needed <strong>for</strong> local acceptance <strong>and</strong> Title 24 accessibility; <strong>and</strong><br />

• A chemical inventory on small projects, if other than new construction <strong>and</strong> remodel<br />

projects that alter the existing structural frame (<strong>for</strong>merly referred to as “H” projects)<br />

occupancy, to show compliance with number <strong>of</strong> control areas <strong>and</strong> maximum allowable<br />

quantities <strong>of</strong> hazardous materials as listed in CBC Tables 307.1(1) <strong>and</strong> 307.1(2) (see<br />

OSHPD PIN 8 <strong>for</strong> required in<strong>for</strong>mation <strong>and</strong> suggested <strong>for</strong>mat).<br />

It is recommended that a tabulation or matrix be provided <strong>for</strong> projects resulting in a change in the<br />

number <strong>of</strong> patient bedrooms, isolation rooms, operating rooms, dietetic storage <strong>and</strong> refrigeration,<br />

general storage, <strong>and</strong> prenatal unit space. Such a tabulation or matrix should include the number<br />

<strong>of</strong> existing items as well as the proposed items. Include a matrix <strong>of</strong> bed count <strong>and</strong> type.<br />

Existing Special Conditions<br />

<strong>Project</strong>s that include additions <strong>and</strong>/or renovations <strong>of</strong> existing spaces within OSHPD-approved<br />

buildings present additional challenges to providing required documentation <strong>for</strong> approval <strong>of</strong> the<br />

project. To assist the reviewer in underst<strong>and</strong>ing how the new work does not conflict with required<br />

levels <strong>of</strong> safety provided by the existing facility, in many cases the drawings will need to fully<br />

describe adjacent uses <strong>and</strong> occupancies, existing construction, <strong>and</strong> prior approvals <strong>and</strong><br />

documentation. Buildings or structures outside the scope <strong>of</strong> work, but proximate to the scope <strong>of</strong><br />

work, should be identified by size, area, height, <strong>and</strong> building <strong>and</strong> construction type.<br />

Often this in<strong>for</strong>mation is unavailable from old drawings but needs to be ascertained by field<br />

investigation <strong>and</strong> measurement. The title sheet can only outline the existing conditions,<br />

occupancies, <strong>and</strong> construction to in<strong>for</strong>m the reviewer <strong>of</strong> in<strong>for</strong>mation that is presented in more<br />

detail with the plans <strong>and</strong> other drawings. However, in the brief descriptions <strong>of</strong> existing facilities,<br />

use <strong>of</strong> the same code-matching terminology is particularly important, <strong>and</strong>, whenever possible,<br />

drawings from previous OSHPD-approved projects <strong>for</strong> the existing facility <strong>and</strong> related work should<br />

be listed <strong>and</strong> attached (<strong>and</strong> specifically called out as “reference only” drawings).<br />

(OSHPD <strong>Best</strong> <strong>Practices</strong>) Page 21 DRAFT FINAL, Sept. 2011