Synchronous Generators BG 132 and BG 160
Synchronous Generators BG 132 and BG 160
Synchronous Generators BG 132 and BG 160
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Synchronous</strong> <strong>Generators</strong> <strong>BG</strong> <strong>132</strong> / <strong>BG</strong> <strong>160</strong><br />
Safety precautions<br />
DANGER<br />
Risk of<br />
personal injury<br />
or death<br />
<strong>and</strong><br />
destruction<br />
hazard<br />
Never connect the generator to the public electricity supply<br />
network or to any other systems for power generation. Risk of<br />
death, fire <strong>and</strong> destruction hazard!<br />
Never connect several generators to each other. Risk of death,<br />
fire <strong>and</strong> destruction hazard!<br />
If the generator shall be connected to an existing power<br />
distribution network (e.g. a house wiring), it has to be<br />
ensured, that the system is completely <strong>and</strong> reliably<br />
disconnected from the public electricity supply network of the<br />
energy supply company. Reverse feeding into the public<br />
electricity supply network or network interconnection is not<br />
allowed. Reverse feeding involves mortal danger by electric<br />
shock for persons possibly working at the de-energized public<br />
electricity supply network. Due to network interconnection<br />
with the public electricity supply network, the generator can be<br />
damaged, burn or cause fire in electrical cables of the system.<br />
Grounding the neutral conductor of the generator (N, midpoint<br />
conductor) supersedes the protective measure "protection<br />
separation" <strong>and</strong> should therefore be avoided. If the neutral<br />
conductor N shall be grounded anyway, this may only be<br />
performed by an electrically qualified person. In this case, a<br />
current-operated earth-leakage circuit breaker has to be<br />
connected on the load side of the generator output. The<br />
efficiency of the electrical protective measure has to be<br />
confirmed by an appropriate measurement.<br />
The generator supplies highly dangerous voltages during<br />
operation! Never touch the generator or the devices connected<br />
to the generator with wet h<strong>and</strong>s during operation. Mortal<br />
danger by electric shock!<br />
Generator components may be very hot, not just during but also<br />
after operation. Burning hazard!<br />
The generator may only be operated with the protective covers<br />
for the drive mounted as specified. Risk of personal injury!<br />
8 Issue date: August 2002