<strong>Synchronous</strong> <strong>Generators</strong> <strong>BG</strong> <strong>132</strong> / <strong>BG</strong> <strong>160</strong><br />

Chapter 4: 4.3 General regulations for installation<br />

After installation, a test finger according to EN 60034, part 5, or a foreign part<br />

with a diameter greater than 12 mm (e.g. a sphere) must not come in contact<br />

with rotating parts, if a risk could result from this. Especially the protective<br />

covers of the power transmission have to be constructed stable <strong>and</strong> mounted<br />

firmly. It must not be possible to remove protective covers without using tools.<br />

The cooling air must be supplied <strong>and</strong> eliminated in a way, that the accumulating<br />

dissipation heat is eliminated definitively. Only harmless amounts of dust <strong>and</strong><br />

water may be sucked with the cooling air. Short-circuits of the air have to be<br />

avoided.<br />

<strong>Generators</strong> with a second shaft end must not be operated without a machine or<br />

protective cover correctly installed to this end.<br />

If the generator is not already equipped ex works with a control box containing<br />

electric protection equipment <strong>and</strong> sockets, adequate fuse equipment has to be<br />

installed in an external control cabinet to protect the circuits (sockets) against<br />

overcurrent <strong>and</strong> short-circuit. Observe that the neutral conductor N has to be<br />

fused as well. Consult the generator manufacturer GTS for the correct types <strong>and</strong><br />

nominal currents of the circuit breakers to be used. Further information about<br />

this can be found in section 4.8 on page 70.<br />

If the generator is not already equipped ex works with a control box containing<br />

electric protection equipment <strong>and</strong> sockets, the generator, the control cabinet<br />

<strong>and</strong> the complete electric installation have to be checked by visual inspection,<br />

testing <strong>and</strong> measurement according to DIN VDE 0100, part 610, before bringing<br />

the generator into operation for the first time.<br />

Observe the specific installation rules <strong>and</strong> instructions for the individual<br />

generator types listed in the following sections of this manual. There you<br />

can also find particular installation notes for the different drive types of the<br />

generators.<br />

• Refer to section 4.5 on page 35 for single-bearing generators of the size<br />

<strong>BG</strong> <strong>132</strong>.<br />

• Refer to section 4.6 on page 49 for two-bearing generators of the size<br />

<strong>BG</strong> <strong>132</strong>.<br />

• Refer to section 4.7 on page 62 for two-bearing generators of the size<br />

<strong>BG</strong> <strong>160</strong>.<br />

• Refer to section 4.8 on page 70 for notes <strong>and</strong> instructions concerning the<br />

electrical connection of the generators.<br />

30 Issue date: August 2002