SUBCON-PLUS-PROFIB…<br />

3.3 Structure<br />

Figure 3<br />

Structure<br />

3.4 Connection<br />

Stripping<br />

Figure 4<br />

!<br />

9 1<br />

7<br />

8<br />

<br />

Stripping<br />

2<br />

34<br />

5<br />

The following stripping tools are re<strong>com</strong>mended for fast and<br />

easy stripping:<br />

PSM-STRIP-FC/PROFIB (Order No. 2744623) and<br />

QUICK-WIREFOX 6 (Order No. 1204384).<br />

6<br />

$<br />

$ &<br />

24 mm<br />

! <br />

6 13 5<br />

1 Upper housing part<br />

2 Slide switch<br />

3 Connection block for in<strong>com</strong>ing bus<br />

4 Connection block for outgoing bus<br />

5 Mounting screws<br />

6 Lower housing part<br />

7 Strain relief<br />

8 PG connection (SUBCON-PLUS-PROFIB/PG/SC 2<br />

only)<br />

9 Housing screws<br />

Cable Entry<br />

SUBCON-PLUS-PROFIB/SC 2 and SUBCON-PLUS-<br />

PROFIB/PG/SC 2 connectors provide the option of cable<br />

entry from the left or from the right. Upon delivery, the<br />

connector is assembled for cable entry from the left.<br />

To ensure reliable operation, observe the<br />

re<strong>com</strong>mended stripping lengths shown in<br />

Figure 4.<br />

Connection with Cable Entry from the Left<br />

• Strip the conductors as shown in Figure 4.<br />

• Unscrew the housing screws and lift off the upper<br />

housing part.<br />

• Screw the stripped conductors in the corresponding<br />

contacts of the connection block.<br />

• Always connect the in<strong>com</strong>ing bus cable (BUS IN) to<br />

terminal connections 1A/1B (even at the start of the bus<br />

system).<br />

• Always connect the outgoing bus cable (BUS OUT) to<br />

terminal connections 2A/2B.<br />

When doing so, take into account the color-coding of<br />

the connection terminals.<br />

• To finish, mount the upper housing part and tighten the<br />

screws. This provides the strain relief for the bus cable.<br />