<strong>UM</strong> <strong>EN</strong> <strong>FLX</strong> <strong>ASI</strong> <strong>SYS</strong> <strong>PRO</strong> <strong>INST</strong><br />

Interference – Signal and power supply cables should not be installed in parallel. If necessary, metal<br />

isolating segments should be placed between the power supply and signal cables.<br />

– During installation, all connector interlocks must be firmly tightened to ensure the best<br />

possible contact.<br />

Cable routing in control<br />

cabinets<br />

– Install AS-i cables in separate cable ducts.<br />

– Install AS-i cables with a minimum distance of 10 cm to power cables.<br />

Cable routing in buildings – Where possible, use metal cable hangers.<br />

– Install AS-i cables as far away as possible from sources of interference, for example,<br />

motors and welding equipment.<br />

6.1 Interference Suppression Measures<br />

Phoenix Contact re<strong>com</strong>mends connecting relay coils or motor coils with an RC element to<br />

protect the devices against interference. Depending on the application, the delay time of the<br />

relay can be increased by approximately 1 ms.<br />

Figure 6-1<br />

5001B301<br />

Relay coil with RC element<br />

For the sizing of the RC element the following values are re<strong>com</strong>mended:<br />

R = 100 Ω to 200 Ω; C=220nFto470nF.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

6-2 PHO<strong>EN</strong>IX CONTACT 7513_en_01