Slaves<br />

4.2.10 Setting the Address for Fieldline Extension<br />

AS-i M8 Devices<br />

Before starting up a system with an AS-Interface system for the first time, all connected<br />

devices must be assigned an operating address. By default upon delivery, all devices have<br />

the address "zero". During address assignment, only one device may be addressed with<br />

"zero".<br />

Address programming via<br />

the master<br />

Address programming<br />

using an addressing<br />

device<br />

Addressing can be performed by the master via the AS-Interface cable. All devices must be<br />

connected individually and addressed directly.<br />

For additional information about address programming, please refer to "Address<br />

Assignment" on page 7-1.<br />

There is also the option of using an addressing device for manual addressing.<br />

To manually set the address of the device, proceed as follows:<br />

• Remove the AS-i round cable from the AS-i connection (1) on the device.<br />

• Connect the addressing device (Order No. 2741338) to the AS-i connection (1) using a<br />

4-pos. unshielded cable with M12 connector.<br />

• At the touch of a button, the address of the connected slave can be read and displayed<br />

on the LCD.<br />

• The address that is returned can be modified using the two arrow buttons in order to<br />

enter the new desired address.<br />

• Press the programming button to save the device address.<br />

• Disconnect the addressing device from the device.<br />

• Connect the AS-i round cable to the AS-i connection on the device.<br />

1<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

Figure 4-25<br />

O<br />

3<br />

O<br />

4<br />

7513A030<br />

Addressing and AS-i connection<br />

For additional information about addressing, please refer to the user manual:<br />

AS-Interface Addressing Device, <strong>ASI</strong> CC ADR <strong>UM</strong> E, Order No. 9013727<br />

7513_en_01 PHO<strong>EN</strong>IX CONTACT 4-23