Slaves<br />
4.1.7 Connecting AS-Interface and the Auxiliary Voltage AUX to<br />
M12 Devices<br />
A<br />
The connection to AS-Interface and the auxiliary voltage AUX is established by inserting the<br />
AS-i flat-ribbon cables in the corresponding cable routing aids in the mounting base of the<br />
device and then contacting the electronics module. Contact is established as soon as the<br />
locking latch snaps in.<br />
Proceed as follows:<br />
• Open the device by releasing the locking latch (A) and then pushing the electronics<br />
module until it engages with a click (B).<br />
• Insert the yellow flat-ribbon cable for the bus in the cable routing aid (AS-i) (C1).<br />
• If necessary, insert the black flat-ribbon cable for the auxiliary voltage AUX in the cable<br />
routing aid (C2).<br />
• Close the device by pushing the electronics module back to its original position until it<br />
engages with a click (D). Then close the locking latch (E). The device is connected to<br />
the AS-i cable(s) using the penetration technique by snapping in the locking latch.<br />
B<br />
Figure 4-10<br />
D<br />
Inserting the AS-i flat-ribbon cable<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
C1<br />
C2<br />
E<br />
7472B004<br />