Slaves<br />
4.1.4 Mounting Fieldline Extension AS-i M12 Devices<br />
Fieldline Extension AS-i devices can be mounted directly on the machine. They can be<br />
screwed onto flat surfaces or snapped onto a DIN rail.<br />
The mounting surface must be flat to avoid strain in the housing when tightening the<br />
screws.<br />
Mounting with<br />
screws<br />
The devices can be mounted directly on the mounting surface using two or more mounting<br />
holes (1) in Figure 4-5. The diameter of the mounting holes is 4 mm, the cylindrical sinking<br />
is 8 mm. For the drill hole spacing, please refer to the dimensional drawings on page 4-3.<br />
Figure 4-5<br />
Front mounting of Fieldline Extension AS-i M12 device<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
2<br />
1 1<br />
7513c010<br />
Tighten the mounting screws on the support plate with a maximum of 0.8 Nm.<br />
Use the protection against unlocking (<strong>FLX</strong> <strong>ASI</strong> M12 FS, Order No. 2773539) to prevent<br />
the device from getting unlocked unintentionally. Screw the protection against unlocking<br />
to one of the mounting holes (1) in Figure 4-5.<br />
2<br />