Power Supply Units<br />

3.5.2 Mounting on the DIN Rail (Flat Mounting Position)<br />

Figure 3-5<br />

Flat mounting position with UTA 107 universal DIN rail adapter<br />

The device is supplied as standard for a narrow mounting position. A flat mounting position<br />

is achieved by mounting the device at a 90° angle to the DIN rail.<br />

To do this, mount the UTA 107 DIN rail adapter as shown in Figure 3-5 (Torx T10 mounting<br />

screws, tightening torque of 0.8 - 0.9 Nm (7 - 8 lb in)). No additional mounting material is<br />

required.<br />

3.6 Connecting the Power Supply Units<br />

The device is equipped with plug-in spring-cage terminals. This enables fast device<br />

connection and visible isolation of the electrical connection, if required.<br />

CAUTION:<br />

Connectors may only be operated when the power is switched off.<br />

The following cable cross-sections can be connected:<br />

Solid [mm 2 ] Stranded [mm 2 ] AWG Stripping Length L [mm]<br />

0.2 - 2.5 0.2 - 2.5 24 - 12 10<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

In order to <strong>com</strong>ply with UL approval, use copper cables that are designed for operating<br />

temperatures > 75°C. For reliable and safe-to-touch connections, strip the cable ends<br />

according to Figure 3-6.<br />

Figure 3-6<br />

Stripping length<br />

NOTE:<br />

Each AS-Interface system may only be supplied by one AS-Interface power supply unit.<br />

7513_en_01 PHO<strong>EN</strong>IX CONTACT 3-5