2.1.6 Power Supply and AS-i Connection Method<br />
AS-Interface Masters/Gateways<br />
The AS-i master does not require a separate power supply. The <strong>com</strong>munications power of<br />
the AS-i master is supplied in full from the Inline Modular local bus. All the power for the ASi<br />
electronics is obtained directly from the AS-i network (current consumption around 200 mA<br />
from AS-i). An additional 24 V power supply is not required for the AS-i master. The AS-i<br />
master is simply integrated in the Inline Modular local bus and connected to the AS-i cable.<br />
The master starts working when the AS-i power supply unit is switched on.<br />
Like all other AS-i <strong>com</strong>ponents, the AS-i power supply unit is connected at any point in the<br />
AS-i network via the AS-i cable, see also "Power Supply Units" on page 3-1.<br />
2.1.7 Diagnostic and Status Indicators<br />
Figure 2-9<br />
,<br />
+ . /<br />
) 5 1<br />
6 4<br />
% " ) !<br />
<strong>ASI</strong> MA IL UNI with appropriate connectors<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
, -<br />
Designation Color Meaning<br />
D Green LED Diagnostics<br />
ON<br />
Bus active<br />
Flashing<br />
0.5 Hz Supply present, bus not active<br />
2 Hz Bus active, I/O error<br />
4 Hz Cable interrupt before the master<br />
OFF No <strong>com</strong>munications power, bus not active<br />
5 - 6<br />
) 5 E<br />
2 4 /<br />
2 4 <br />
7513_en_01 PHO<strong>EN</strong>IX CONTACT 2-7