1.7 System Components of the AS-Interface System<br />

An AS-i system consists of at least the <strong>com</strong>ponents described below.<br />

1.7.1 Masters/Gateways<br />

Slave profile<br />

An AS-i master (gateway) is used to integrate an AS-i system into a higher-level fieldbus.<br />

These are "intelligent" units in the AS-i system, which are responsible for serial<br />

<strong>com</strong>munication and self-diagnostics in the system. For the control system or in the higherlevel<br />

network, the AS-i system is represented in the corresponding process data, which can<br />

be accessed in the normal way.<br />

1.7.2 Power Supply Units<br />

AS-Interface networks are supplied by special power supply units. These power supply<br />

units provide as DC voltage of 29.5 V to 31.6 V at the output side. This is necessary in order<br />

to safely operate all the sensors and actuators with the 24 V nominal voltage in the AS-i<br />

system. In addition, with an integrated data decoupling network the power supply unit<br />

ensures that data can superimpose the supply voltage. AS-i power supply units meet the<br />

requirements of "functional extra-low voltages with safe isolation (PELV)". Outputs are<br />

usually supplied separately via a black power cable. These standard power supply units<br />

must also meet the requirements of PELV. This ensures that in the event of a device fault<br />

the AS-i system cannot output any hazardous voltages.<br />

1.7.3 Slaves<br />

Through the concentration of special AS-i functions in the <strong>com</strong>pact protocol chip a wide<br />

range of termination devices can be adapted for use in the AS-i system. These termination<br />

devices are the devices on the bus, i.e., the slaves. I/O devices are AS-i slaves, which<br />

integrate several devices of conventional (parallel) type in AS-i systems.<br />

Each slave is identified by a slave profile. The slave profile is used for clear, functional<br />

identification by the AS-i master. The specifications for this are defined in the AS-Interface<br />

specification and <strong>com</strong>prise an ID code, two extended ID codes (ID1 code and ID2 code),<br />

and a configuration code for inputs/outputs (IO code). This data indicates the function of the<br />

slave.<br />

The slave profile looks like this: S-7.A.0. It <strong>com</strong>prises the IO code, ID code, and ID2 code, it<br />

cannot be modified and is permanently programmed by the manufacturer.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

All information in the slave profile (ID, ID1, ID2, and IO code) is required in order to easily<br />

replace slaves within an existing system. The master uses this data to check whether the<br />

actual configuration matches the desired configuration.<br />