0D27<br />

Code Type Description and Remedy<br />

0D14 LB<br />

0D15<br />

0D16<br />

0D17<br />

0D18 LB<br />

0D19<br />

0D1A<br />

0D1B<br />

0D1C LB<br />

0D1D<br />

0D1E<br />

0D1F<br />

0D20 LB<br />

0D21<br />

0D22<br />

0D23<br />

0D24 LB<br />

0D25<br />

0D26<br />

0D27<br />

Multiple errors in the segment of the indicated<br />

device caused by transmission errors.<br />

Remedy: Check the segment:<br />

– Shielding of the bus cables (connectors)<br />

– Grounding/equipotential bonding<br />

– Faulty connectors or joints<br />

– Voltage dips on the <strong>com</strong>munications power for<br />

remote bus devices<br />

– Faulty fiber optic assembly<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Multiple timeout in the segment of the indicated<br />

device caused by transmission errors.<br />

Remedy:See Error Code 0D14 on page 93.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Transmission error (CRC error) on the data<br />

forward path of the in<strong>com</strong>ing bus interface (IN) of<br />

the indicated device.<br />

Remedy: See Error Code 0D14.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Interruption of the data forward path to the bus<br />

interface (IN) of the indicated device<br />

Remedy: Check the cables, connectors, and<br />

INTERBUS connections for interruptions.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Transmission error (CRC error) on the data return<br />

path of the in<strong>com</strong>ing bus interface (IN) of the<br />

indicated device.<br />

For Loop devices: Transmission path from the last<br />

device to the bus terminal module.<br />

Remedy: See Error Code 0D14 on page 93.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />