0C90<br />
Code Type Description and Remedy<br />
0C90 OUT1<br />
0C91<br />
0C92<br />
0C93<br />
The device could not activate the bus segment<br />
that followed it, as it executed a voltage reset or is<br />
faulty.<br />
Remedy:<br />
1. Check the device.<br />
2. Check the voltage supply of the device to<br />
determine whether it conforms to the nominal<br />
value and whether the permissible AC<br />
<strong>com</strong>ponent was exceeded (see<br />
corresponding data sheet).<br />
3. Check the power supply unit of this bus<br />
terminal module for overload (see<br />
corresponding data sheet).<br />
Add_Error_Info: Error location<br />
(Segment . Position).<br />
0C94 OUT1 A local bus device was detected at the outgoing<br />
0C95 remote interface (OUT1) of the indicated device.<br />
0C96 Remedy: Connect remote bus device.<br />
0C97 Add_Error_Info: Error location<br />
(Segment . Position).<br />
0C98 OUT1 The device connected to the outgoing remote bus<br />
0C99 interface (OUT1) of the indicated device is not<br />
0C9A known (i.e., it has an invalid ID code).<br />
0C9B Remedy: Replace the device.<br />
Add_Error_Info: Error location<br />
(Segment . Position).<br />
0CA0<br />
An attempt was made to parameterize a bus for<br />
isolated disconnection, which does not contain<br />
only SUPI 3 devices.<br />
Remedy: Only use SUPI 3 devices.<br />