0C90<br />

Code Type Description and Remedy<br />

0C90 OUT1<br />

0C91<br />

0C92<br />

0C93<br />

The device could not activate the bus segment<br />

that followed it, as it executed a voltage reset or is<br />

faulty.<br />

Remedy:<br />

1. Check the device.<br />

2. Check the voltage supply of the device to<br />

determine whether it conforms to the nominal<br />

value and whether the permissible AC<br />

<strong>com</strong>ponent was exceeded (see<br />

corresponding data sheet).<br />

3. Check the power supply unit of this bus<br />

terminal module for overload (see<br />

corresponding data sheet).<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

0C94 OUT1 A local bus device was detected at the outgoing<br />

0C95 remote interface (OUT1) of the indicated device.<br />

0C96 Remedy: Connect remote bus device.<br />

0C97 Add_Error_Info: Error location<br />

(Segment . Position).<br />

0C98 OUT1 The device connected to the outgoing remote bus<br />

0C99 interface (OUT1) of the indicated device is not<br />

0C9A known (i.e., it has an invalid ID code).<br />

0C9B Remedy: Replace the device.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

0CA0<br />

An attempt was made to parameterize a bus for<br />

isolated disconnection, which does not contain<br />

only SUPI 3 devices.<br />

Remedy: Only use SUPI 3 devices.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />