06.05.2014 Views

interbus - Onlinecomponents.com

interbus - Onlinecomponents.com

interbus - Onlinecomponents.com

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

0C79<br />

Code Type Description and Remedy<br />

0C6C DEV<br />

0C6D<br />

0C6E<br />

0C6F<br />

0C70 DEV<br />

0C71<br />

0C72<br />

0C73<br />

0C74 DEV<br />

0C75<br />

0C76<br />

0C77<br />

0C78 RB<br />

The indicated device executed a reset due to a<br />

fault or insufficient voltage supply.<br />

Remedy:<br />

– Check the device.<br />

– Check the voltage supply to determine<br />

whether it conforms to the nominal value and<br />

whether the permissible AC <strong>com</strong>ponent was<br />

exceeded.<br />

– Check the power supply unit of the bus<br />

terminal module for overload (see<br />

corresponding data sheet).<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

The controller board tried to start up the bus<br />

before all devices were ready for operation.<br />

Remedy:<br />

– Replace the device.<br />

– Delay the call of the "Activate_Configuration"<br />

service (0711 hex ).<br />

– Increase the startup delay using CMD or PC<br />

WORX software.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

An invalid operating mode has been set on the<br />

INTERBUS protocol chip of a device.<br />

Remedy: Replace the device or set a valid<br />

operating mode.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

The data length of the indicated device is not<br />

identical to the configuration frame when the<br />

dynamic PCP channel is switched on<br />

(“ page 116).<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

0C79 RB<br />

The ID code of the indicated device is not identical<br />

to the configuration frame when the dynamic PCP<br />

channel is switched on (“ page 116).<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

5277CC01 87